| Notes |
| Date |
Text |
| 2009-01-20 18:04:03 | | | | | | | | | | APPLICATION #08120538 ELECTRICAL PLAN REVIEW | | | 219 SOUTH OLIVE AVENUE 1/20/09 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | THESE ARE REPEAT COMMENTS FROM THE PREVIOUS REVIEW WITH | | | THE SAME COMMENT NUMBER. | | | | | | 2} SHEETS E-1 AND E-2 STILL LIST THE ADDRESS AS 307 | | | EVERNIA STREET. SEE ADDRESSING COMMENTS. | | | | | | 3} THE REVERENCED CODES IN NOTE #1, SHEET E-2 ARE | | | INCORRECT, 2006-NFPA 101 (SHOULD BE 2003) AND 2007 | | | NFPA-72 SHOULD BE 2002. SEE CHAPTER 35 FBC. | | | | | | NEW COMMENT SHEETS A-1, A-2, E-1: | | | | | | 1} THE PARTITION PREP AREA WALL ON THE FLOOR PLAN OF | | | THE ???A??? SHEETS DOES NOT MATCH THE LAYOUT ON SHEET | | | E-1. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | |
|