| 2009-01-06 16:34:52 | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR ALL NEW |
| | EQUIPMENT. THE EQUIPMENT MAY NOT BE FED FROM GENERAL |
| | PURPOSE RECEPTACLES OR CIRCUITS. |
| | PLEASE SHOW ALL CIRCUITING ON PLANS AND COORDINATE WITH |
| | A PANEL SCHEDULE TO BE SUBMITTED. |
| | PLEASE BE SURE TO INCLUDE ALL NEW LOADS WITH THE |
| | EXISTING LOADS FOR THE PANEL/SERVICE WHICH SUPPLIES |
| | POWER TO SPACE. |
| | 220, 310, 240, 408.4 ETC |
| | CODE SECTIONS ARE GENERAL AS THERE WERE NO ELECTRICAL |
| | PLANS SUBMITTED. |
| | |
| | 2) NOTE: PLEASE INDICATE THE CORRECT APPLIED LOCATION |
| | OF THE PERMITTED WORK ON THE PLANS. THE LOCATION STATES |
| | 307 EVERNIA HOWEVER THE APPLIED LOCATION IS 219 S |
| | OLIVE. |
| | INFORMATION WAS ROUTED TO THE ADDRESSING REVIEWER. ONCE |
| | THE FINAL SUITE/UNIT DETERMINATION IS DONE PLEASE BE |
| | SURE TO REVISED TITLE BLOCKS ACCORDINGLY. |
| | FAC 61G1-16.004, FBC 106.5 |
| | |
| | 3) NOTE: PLEASE BE SURE TO INDICATE THE FOLLOWING CODES |
| | ON PLANS FOR MINIMUM DESIGN. |
| | FBC 2004W/2007 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 4) NOTE: PLEASE SEE CHAPTER 13 FOR ANY PRESCRIPTIVE |
| | REQUIREMENTS. |
| | 13-415.1, 13-415.2. ETC |
| | THERE IS NO LIGHTING SHOWN ON PLANS. |
| | AS THE LAYOUT OF EQUIPMENT, COUNTERS ETC IS BEING |
| | RELOCATED PLEASE SHOW NEW OR EXISTING LIGHTING. |
| | |
| | 5) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9 FOR MINIMUM |
| | REQUIRED LIGHTING FOR EGRESS. |
| | NEW OR EXISTING? |
| | |
| | 6) NOTE: AS NOTED IN NOTE #1 ABOVE PLEASE BE SURE ALL |
| | CONTINUOUS LOADS ARE SHOWN AT 125%. |
| | 215.3,230.42, 422.13 ETC |
| | |
| | *** AS NO ELECTRICAL WAS SUBMITTED THERE MAY VERY WELL |
| | BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |