Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-01-12 22:52:49*****DENIED****
  
  
 1. THE ACTUAL SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. KNOX LOCKING CAPS WILL REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS. INCLUDE COMMENT TO AN
 APPROPIATE PLAN SHEET. FOR APPLICATIONS CONTACT WEST
 PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
  
 3. IN ADDITION TO ELECTRONIC SWITCHES, CHAIN AND LOCK
 WILL BE REQUIRED ON THE DOUBLE DETECTOR CHECK VALVE
 ASSEMBLY. INCLUDE COMMENT ON AN APPROPIATE PLAN SHEET.
  
 4. A FIRE SPRINKLER PIPE INSPECTION (CODE:603) SHALL BE
 REQUIRED AS PER WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT.
  
 5. SAFETY MARGIN ON THE SPRINKLER SYSTEM SHALL BE NO
 LESS THAN 5.0 PSI; HYDRAULIC CALCULATIONS SHOWS A PSI
 OF 2.492 ON PAGE 2 OF FP4 - 5TH FLOOR CORRIDOR .
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722