Plan Review Notes
Plan Review Notes For Permit 08120508
Permit Number 08120508
Review Stop E
Sequence Number 2
Notes
Date Text
2009-04-09 15:41:01** DENIED**
  
 1) NOTE: 2ND TIME, NO DESIGNER OF RECORD ON PLANS.
 PLEASE SEE FS 481.229, 471.003 WHEN MEETING EXCEPTIONS
 DESIGNER/ PERSON RESPONSIBLE FOR PLANS MUST PRINT
 NUMBER, ANY LICENSE NUMBER AND SIGN PLANS.
 PLANS DO NOT SHOW ANY DESIGNER OF RECORD.
  
 2) NOTE: 2ND TIME: PLANS SHOW A 5KW INSTANT TYPE WATER
 HEATER HOWEVER A 5KW UNIT WILL NOT HEAT WATER IN A
 HOUSE OF THIS SIZE. TYPICALLY A 5KW UNIT INSTANT TYPE
 APPLIANCE WILL BE FOR A SINGLE POINT OF USE ONLY.
 PLEASE ALSO SEE THE PANEL SCHEDULE STATES 50AMP
 BREAKER. IF THE UNIT WAS 5KW THE 50AMP OCP IS TOO HIGH
 PER 422.11.
 PLEASE SEE LISTING OF UNIT BEING PROPOSED. 110.3
 240.4,310.16 AND PLEASE BE SURE TO REVISE LOAD
 CALCULATIONS ACCORDING TO NEW UNIT.
  
 3) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW ALSO AS
 ALL REQUIRE SMALL APPLIANCE TYPE CIRCUITS. PLANS SHOW
 ALL COUNTER SPACE GFI RECEPTACLES ON ONE OF THE SMALL
 APPLIANCE CIRCUITS. THIS COULD HAVE BEEN A REDLINED
 ITEM HOWEVER PLANS ARE COMING BACK FOR OTHER COMMENTS.
 SEE 210.11C1, 210.52B1, 220.53
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  