| 2009-04-09 15:41:01 | ** DENIED** |
| | |
| | 1) NOTE: 2ND TIME, NO DESIGNER OF RECORD ON PLANS. |
| | PLEASE SEE FS 481.229, 471.003 WHEN MEETING EXCEPTIONS |
| | DESIGNER/ PERSON RESPONSIBLE FOR PLANS MUST PRINT |
| | NUMBER, ANY LICENSE NUMBER AND SIGN PLANS. |
| | PLANS DO NOT SHOW ANY DESIGNER OF RECORD. |
| | |
| | 2) NOTE: 2ND TIME: PLANS SHOW A 5KW INSTANT TYPE WATER |
| | HEATER HOWEVER A 5KW UNIT WILL NOT HEAT WATER IN A |
| | HOUSE OF THIS SIZE. TYPICALLY A 5KW UNIT INSTANT TYPE |
| | APPLIANCE WILL BE FOR A SINGLE POINT OF USE ONLY. |
| | PLEASE ALSO SEE THE PANEL SCHEDULE STATES 50AMP |
| | BREAKER. IF THE UNIT WAS 5KW THE 50AMP OCP IS TOO HIGH |
| | PER 422.11. |
| | PLEASE SEE LISTING OF UNIT BEING PROPOSED. 110.3 |
| | 240.4,310.16 AND PLEASE BE SURE TO REVISE LOAD |
| | CALCULATIONS ACCORDING TO NEW UNIT. |
| | |
| | 3) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW ALSO AS |
| | ALL REQUIRE SMALL APPLIANCE TYPE CIRCUITS. PLANS SHOW |
| | ALL COUNTER SPACE GFI RECEPTACLES ON ONE OF THE SMALL |
| | APPLIANCE CIRCUITS. THIS COULD HAVE BEEN A REDLINED |
| | ITEM HOWEVER PLANS ARE COMING BACK FOR OTHER COMMENTS. |
| | SEE 210.11C1, 210.52B1, 220.53 |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |