| 2009-01-13 10:02:17 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 EXISTING BUILDING |
| | FBC-2004 RESIDENTIAL |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHTS 2.1 & 3.1. THE PROPOSED FLOOR PLAN SHOWS THE |
| | WASH MACHINE, BUT THE DEMO SHEET SHOWS NO EXISTING WASH |
| | MACHINE CONNECTIONS TO THE SANITARY. PLEASE INDICATE |
| | THE LOCATION OF THE EXISTING WASH MACHINE TO DETERMINE |
| | IF THE SANITARY HAS BEEN DEMO'D ACCORDING TO SECTION |
| | 704.5. SECTION 106.1.2.. |
| | |
| | 2. SHT 2.1 DEMO NOTE NUMBER 8. A GAS PERMIT IS REQUIRED |
| | FOR THE GAS DEMO WORK. PLEASE INDICATE THE LOCATION OF |
| | THE GAS PIPING WORK ON THE EXISTING FLOOR PLAN DEMO. |
| | SECTION 106.1.2. |
| | |
| | 3. SHT 3.1. A WATER HEATER IS REQUIRED. SECTION 607.1. |
| | SHOW THE LOCATION OF THE WATER HEATER ON THE FLOOR |
| | PLAN. SECTION 106.1.2. |
| | |
| | 4. SHT 6.1 DETAIL 3/6.1 SANITARY RISER DIAGRAM. THE |
| | BRANCH LINE TO THE WASH MACHINE IS REQUIRED TO BE 3" |
| | PER SECTION 406.3. PLEASE INDICATE PIPE SIZE ON RISER |
| | DIAGRAM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |