| 2008-12-31 11:25:38 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE FS 481.229, 471.003. WHEN MEETING |
| | EXCEPTIONS IN THE STATUTES AS MENTIONED PLANS ARE STILL |
| | REQUIRED TO BE DONE BY THE DESIGN PROFESSIONAL AS |
| | LISTED. |
| | THE PLANS SUBMITTED DO NOT CONTAIN ANY TITLE BLOCKS, |
| | PRINTED NAME, SIGNATURE, OR SIGNED AND SEALED. |
| | |
| | 2) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR |
| | REQUIRED LOADS ON CIRCUITS FOR SMALL APPLIANCES, DINING |
| | AND BREAKFAST ROOM. THE TWO SMALL APPLIANCE CIRCUITS |
| | ARE SHOWN WITH THE 1.5KVA HOWEVER NOT THE OTHER TWO. |
| | |
| | 3) NOTE: PLEASE SEE 210.63,210.8A FOR MISSING GFI FOR |
| | CONDENSING UNIT. |
| | |
| | 4) NOTE: PLEASE VERIFY THE SIZE OF THE PROPOSED |
| | INSTA-HOT. IT IS NOT TYPICAL THAT THIS SMALL OF THIS |
| | TYPE OF UNIT WILL FEED ALL LOCATIONS ON THE PLANS AS |
| | SHOWN. |
| | THE MANUFACTURE OF THE EQUIPMENT SHOULD HAVE |
| | INFORMATION ON THE SIZE OF THE UNIT AND HOW THIS WILL |
| | WORK WITH PROPOSED. |
| | THIS IS ONLY NOTED AS THIS IS NOT AN ELECTRICAL |
| | VIOLATION AS SHOWN ON PLANS. |
| | HOWEVER IF THE UNIT IS INDEED LARGER WITH THE KW RATING |
| | THE SIZE OF THE BRANCH CIRCUIT, THE LOAD AND THE OVER |
| | CURRENT PROTECTION WILL NEED TO BE REVISED. |
| | 220,310,240, ETC. |
| | PLEASE VERIFY WITH THE LISTED EQUIPMENT.110.3 |
| | PLEASE SEE 110.26 FOR MINIMUM CLEARANCE REQUIREMENTS. |
| | |
| | 5) NOTE: PLEASE SEE 210.8A7 FOR REQUIRED GFI PROTECTION |
| | OF ALL 15/20AMP RECEPTACLES WITHIN 6FT OF A LAUNDRY |
| | SINK. THIS WAS A CHANGE IN THE 2005 NEC AND IS REQUIRED |
| | EVEN FOR DEDICATED WASHER CIRCUITS. |
| | |
| | 6) NOTE: RISER IS MISSING THE REQUIRED EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO SUB PANEL. |
| | 250.6,250.24,250.110, ETC SIZE PER 250.122. |
| | |
| | 7) NOTE: PLEASE COORDINATE RISER AND PANEL. PANEL IS |
| | SHOWN AS MLO YET RISER INDICATES MAIN. |
| | 240,230. FBC 106.1.1 FOR CLARITY OF PLANS AND |
| | COORDINATION. |
| | |
| | 8) NOTE; PLEASE INDICATE THE REQUIRED LIGHT FIXTURES AT |
| | EGRESS LOCATIONS WHICH ARE SHOWN AS *J* FOR JUNCTION |
| | BOX AT THIS TIME. SOME SORT OF LIGHT FIXTURE WILL BE |
| | REQUIRED. |
| | 210.70, LS101 7.8 |
| | |
| | 9) NOTE: PLANS SHOW BOTH DISPOSAL AND DISHWASHER ON |
| | SEPARATE RECEPTACLES WHICH IS OK HOWEVER PLEASE BE SURE |
| | TO SEE 210.4B. PLEASE CLARIFY IF THE DISPOSAL IS GOING |
| | TO SELF ACTUATED OR THERE WILL BE SWITCHED RECEPTACLE. |
| | 300. |
| | FBC 106.1.1 FOR CLARITY, COORDINATION AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 10) NOTE: SOME LOCATIONS ON PLANS INDICATE THE ENTIRE |
| | RECEPTACLE BEING SWITCHED. THIS IS OK HOWEVER IF THIS |
| | IS THE CASE AN ADDITIONAL RECEPTACLE MEETING 210.52 IS |
| | REQUIRED. IF THESE ARE ACTUALLY HALF SWITCHED |
| | RECEPTACLES PLEASE ADJUST SYMBOL BEING SHOWN. THE |
| | SYMBOL LEGEND DOES CONTAIN A HALF SWITCH RECEPTACLE |
| | SYMBOL. |
| | FBC 106.1.1. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |