2008-12-31 11:25:38** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FS 481.229, 471.003. WHEN MEETING
 EXCEPTIONS IN THE STATUTES AS MENTIONED PLANS ARE STILL
 REQUIRED TO BE DONE BY THE DESIGN PROFESSIONAL AS
 LISTED.
 THE PLANS SUBMITTED DO NOT CONTAIN ANY TITLE BLOCKS,
 PRINTED NAME, SIGNATURE, OR SIGNED AND SEALED.
  
 2) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR
 REQUIRED LOADS ON CIRCUITS FOR SMALL APPLIANCES, DINING
 AND BREAKFAST ROOM. THE TWO SMALL APPLIANCE CIRCUITS
 ARE SHOWN WITH THE 1.5KVA HOWEVER NOT THE OTHER TWO.
  
 3) NOTE: PLEASE SEE 210.63,210.8A FOR MISSING GFI FOR
 CONDENSING UNIT.
  
 4) NOTE: PLEASE VERIFY THE SIZE OF THE PROPOSED
 INSTA-HOT. IT IS NOT TYPICAL THAT THIS SMALL OF THIS
 TYPE OF UNIT WILL FEED ALL LOCATIONS ON THE PLANS AS
 SHOWN.
 THE MANUFACTURE OF THE EQUIPMENT SHOULD HAVE
 INFORMATION ON THE SIZE OF THE UNIT AND HOW THIS WILL
 WORK WITH PROPOSED.
 THIS IS ONLY NOTED AS THIS IS NOT AN ELECTRICAL
 VIOLATION AS SHOWN ON PLANS.
 HOWEVER IF THE UNIT IS INDEED LARGER WITH THE KW RATING
 THE SIZE OF THE BRANCH CIRCUIT, THE LOAD AND THE OVER
 CURRENT PROTECTION WILL NEED TO BE REVISED.
 220,310,240, ETC.
 PLEASE VERIFY WITH THE LISTED EQUIPMENT.110.3
 PLEASE SEE 110.26 FOR MINIMUM CLEARANCE REQUIREMENTS.
  
 5) NOTE: PLEASE SEE 210.8A7 FOR REQUIRED GFI PROTECTION
 OF ALL 15/20AMP RECEPTACLES WITHIN 6FT OF A LAUNDRY
 SINK. THIS WAS A CHANGE IN THE 2005 NEC AND IS REQUIRED
 EVEN FOR DEDICATED WASHER CIRCUITS.
  
 6) NOTE: RISER IS MISSING THE REQUIRED EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO SUB PANEL.
 250.6,250.24,250.110, ETC SIZE PER 250.122.
  
 7) NOTE: PLEASE COORDINATE RISER AND PANEL. PANEL IS
 SHOWN AS MLO YET RISER INDICATES MAIN.
 240,230. FBC 106.1.1 FOR CLARITY OF PLANS AND
 COORDINATION.
  
 8) NOTE; PLEASE INDICATE THE REQUIRED LIGHT FIXTURES AT
 EGRESS LOCATIONS WHICH ARE SHOWN AS *J* FOR JUNCTION
 BOX AT THIS TIME. SOME SORT OF LIGHT FIXTURE WILL BE
 REQUIRED.
 210.70, LS101 7.8
  
 9) NOTE: PLANS SHOW BOTH DISPOSAL AND DISHWASHER ON
 SEPARATE RECEPTACLES WHICH IS OK HOWEVER PLEASE BE SURE
 TO SEE 210.4B. PLEASE CLARIFY IF THE DISPOSAL IS GOING
 TO SELF ACTUATED OR THERE WILL BE SWITCHED RECEPTACLE.
 300.
 FBC 106.1.1 FOR CLARITY, COORDINATION AND ADDITIONAL
 INFORMATION.
  
 10) NOTE: SOME LOCATIONS ON PLANS INDICATE THE ENTIRE
 RECEPTACLE BEING SWITCHED. THIS IS OK HOWEVER IF THIS
 IS THE CASE AN ADDITIONAL RECEPTACLE MEETING 210.52 IS
 REQUIRED. IF THESE ARE ACTUALLY HALF SWITCHED
 RECEPTACLES PLEASE ADJUST SYMBOL BEING SHOWN. THE
 SYMBOL LEGEND DOES CONTAIN A HALF SWITCH RECEPTACLE
 SYMBOL.
 FBC 106.1.1.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  