Plan Review Notes
Plan Review Notes For Permit 08120508
Permit Number 08120508
Review Stop B
Sequence Number 1
Notes
Date Text
2009-01-16 17:04:57RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 **NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY TO CHECK IF IMPACT FEES ARE DUE. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) STORM SHUTTERS:
 *PROVIDE COMPLETE PRODUCT APPROVAL REPORT AND MAKE SURE
 DRAWINGS MATCH FLORIDA PRODUCT APPROVAL REPORT.
 DRAWINGS SUBMITTED (05-270) DON'T MATCH FLORIDA PRODUCT
 APPROVAL FL6968.
  
 **PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED
 SAMPLE. AND CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC
 MOUNTING CONDITIONS WALL SECTION (EG: WALL MOUNT, BUILD
 OUT, ETC) AND SPECIFIC ANCHOR TYPE AND SPACING TO BE
 USED TO VERIFY COMPLIANCE WITH THE PRODUCT AND
 CALCULATED DESIGN PRESSURES.
 NOTE: SEE REVISED DESIGN PRESSURES PRIOR TO COMPLETING
 INSTALLATION SCHEDULE. SEE ITEM 10B BELOW.
  
 B) "INSWING" ENTRY DOOR AS SHOWN ON FLOOR PLANS.
 CLARIFY IF PRODUCT APPROVAL FL5114 SUBMITTED IS THE ONE
 GOING TO BE INSTALLED ON THE FRONT DOOR.
 NOTE: THIS DOOR REQUIRES SHUTTERS. COORDINATE WITH ITEM
 #3A ABOVE.
  
 C) PAIR OF FRENCH DOORS AS SHOWN ON PLANS. NONE
 SUBMITTED AT THIS TIME.
  
 D) FLAT ROOF ASSEMBLY. PRODUCT APPROVAL SUBMITTED (NOA
 06-0105.04) IF FOR CLAY ROOFING TILE. THERE IS NOT CLAY
 TILE SHOWN ON DRAWINGS. ALSO, THE OTHER PRODUCT
 APPROVAL SUBMITTED (NOA 06-0113.03) IS FOR PITCHED ROOF
 UNDERLAYMENT ONLY.
 NOTE: ON FLAT ROOF PRODUCT APPROVAL SPECIFY AND PROVIDE
 THE FOLLOWING:
 *CLEARLY SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. SEE LIST OF APPROVED ASSEMBLIES ON PRODUCT
 APPROVAL.
  
 **CLEARLY SPECIFY WHICH FASTENING OPTION IS GOING TO BE
 USED TO FASTEN THE FLAT ROOF BASE SHEET.
  
 ***PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 FOR NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS. SEE GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA. IF CALCULATIONS NEED TO BE SIGNED AND SEALED, THEN
 PROVIDE SUCH INFORMATION SIGNED AND SEALED.
 NOTE: GENERAL LIMITATION #9 CAN'T BE USED IN THIS JOB.
  
 E) SINGLE HUNG WINDOWS. INFORMATION SUBMITTED IS
 MISSING THE PRODUCT APPROVAL COVER PAGE WITH THE
 FLORIDA PRODUCT APPROVAL NUMBER.
 ALSO, DRAWINGS ARE NOT LEGIBLE. NEED TO PROVIDE LEGIBLE
 DRAWINGS.
  
 F) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 G) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND SHEET WHERE THE CONNECTOR IS SHOWN. THIS
 APPLIES TO CONNECTORS ONLY. OTHER PRODUCT APPROVALS
 NEED TO PROVIDE COMPLETE REPORT. VISIT
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL FLORIDA PRODUCT
 APPROVALS.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5- BRING ALL REVISED PLANS FOR HISTORIC REVIEW APPROVAL
 STAMP PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 6- SHEET 2.1: CLARIFY WHY THERE IS NOT FILLED CELLS AND
 VERTICAL REINFORCEMENT SHOWN ON SOUTH WALL.
 ALSO, SPECIFY VERTICAL REINFORCEMENT SPACING ON THE
 OTHER WALLS AS REQUIRED BY SEC. R609.3.3 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7 SHEET 3.1: REVISE DESIGN PARAMETERS SPECIFICATIONS.
 REFERENCE ASCE 7-02 WHICH IS THE CURRENT CODE, NOT ASCE
 7-05.
  
 8- SHEET 4.1:
 A) CLARIFY WHAT'S CONNECTOR #22. SHOWN ON ROOF FRAMING
 PLAN. WHAT'S LUS10 AS SHOWN ON CONNECTOR SCHEDULE?.
  
 B) SPECIFY SIZE OF NEW 2 PLY GIRDER SHOWN ON ROOF
 FRAMING PLAN WHERE EXISTING ROOF MEETS NEW ROOF.
 ALSO, SPECIFY CONNECTION AT BOTH ENDS TO VERIFY
 COMPLIANCE WITH CALCULATED UPLIFT PRESSURES OF SEC.
 R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) CLARIFY WHY IS THERE A NOTE ON ROOF FRAMING PLAN
 SAYING AREA OF REMODEL AND 2ND FLOOR. THIS IS ONLY A
 ONE STORY CONSTRUCTION.
  
 D) COMPONENT AND CLADDING PRESSURE ZONES IS MISSING THE
 NAILING AT INTERMEDIATE SUPPORTS FOR ROOF ZONE #3. SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 MIN. TYPE AND NAILING REQUIRED FOR ROOF ZONE #3.
  
 E) REVISE/CLARIFY GENERAL ROOF NOTE #7. COORDINATE WITH
 ITEM 9D ABOVE.
  
 F) NEED TO PROVIDE ROOF CROSS VENTILATION AS REQUIRED
 BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. THERE
 ARE 2 VENTILATION OPENINGS SPECIFIED. THEY DON'T
 PROVIDE ROOF CROSS VENTILATION BECAUSE ROOF FRAMING
 PLANS SHOWS 2X12 SOLID ROOF RAFTERS.
  
 G) CLARIFY SIZE OF ROOF SCUPPERS. ROOF DRAIN SECTION
 CALLS FOR 4"X12" SCUPPERS, WHILE NOTE BY ROOF FRAMING
 PLAN CALLS FOR 6"X14" SCUPPERS.
  
 9- SHEET 5.1:
 A) EXTERIOR DOOR HEAD JAMB DETAIL. REVISE SIZE OF
 STRUCTURAL BUCK. 2X4 STRUCTURAL BUCK IS NOT ADEQUATE TO
 PROVIDE DOOR FRAME FULL SUPPORT AS REQUIRED BY SEC.
 R613.6 OF 2004 FLORIDA RESIDENTIAL CODE. ALSO, SEE
 PRODUCT APPROVAL FOR FRAME SIZE.
  
 B) DESIGN PRESSURES SHOWN ON COMPONENTS AND CLADDING
 DON'T CORRESPOND TO EXPOSURE "C". REVISE DESIGN
 PRESSURES AS REQUIRED.
  
 C) CLARIFY WHY ALL EXTERIOR ELEVATIONS MAKE REFERENCE
 TO NEW 2ND STORY. THERE IS NO 2 STORY CONSTRUCTION ON
 THIS PROJECT.
  
 10- SHEET 6.1, TYPICALL WALL SECTION:
 A) CLARIFY SPECS GIVEN FOR THE FLAT ROOF ASSEMBLY. SEE
 PRODUCT APPROVAL FOR CORRECT INFORMATION. INFORMATION
 SUBMITTED IS FOR PITCHED ROOFS, NOT FOR LOW SLOPE
 ROOFS. REVISE AS REQUIRED.
  
 B) REVISE INFORMATION REGARDING ROOF TRUSSES AT
 24"O.C.. SEE ROOF FRAMING PLAN FOR FRAMING MEMBERS
 SPECIFIED.
  
 C) SPACING FOR 2X10 LEDGER ANCHORS DON'T MATCH
 INFORMATION GIVEN ON ROOF FRAMING PLAN. REVISE AS
 REQUIRED.
  
 D) REVISE NOTE REGARDING TWO STORY CONSTRUCTION.
  
 11- REVISE ENERGY CALCULATIONS:
 A) PROVIDE PROJECT ADDRESS AND COMPLETE ALL THE
 INFORMATION ON TOP OF FORM.
  
 B) ARE THE ENERGY CALCULATIONS FOR THE ENTIRE HOUSE OR
 FOR AREA OF WORK ONLY. IS NEW INSULATION PROVIDED FOR
 THE ENTIRE HOUSE IN WALLS AND CEILINGS. ALSO, SEE TYPE
 OF WALLS ON EXISTING STRUCTURE. THIS INFORMATION IS NOT
 SHOWN ON PLANS.
  
 C) PROVIDE COMPLETE MANUFACTURER'S SPECIFICATIONS
 SHOWING THE U-FACTOR AND SHGC FACTOR SHOWN ON ITEMS 7A
 AND 7B WHEN THE DEFAULT FACTOR IS NOT USED. (IN
 ADDITION WINDOWS AND DOORS NEED TO SHOW SUCH RATING FOR
 INSPECTION AFTER INSTALLATION).
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 12- SOIL TEST REPORT SUBMITTED TO BE ADDRESSED TO
 CORRECT BUILDING DEPARTMENT AND ADDRESS. THIS IS THE
 CITY OF WEST PALM BEACH, NOT PALM BEACH COUNTY. AND
 CORRECT ADDRESS IS 200 2ND STREET, WPB, FL 33401.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved