| 2009-11-05 16:47:22 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW FOURTH |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600 OF 2004 FBC. NEED TO PROVIDE REVISED FORM 2004R. |
| | ENERGY CALCULATIONS SUBMITTED ARE FOR 2001 CODE AND |
| | THESE WERE THE ONES THAT WERE REJECTED ON PREVIEWS |
| | REVIEW BECAUSE OF THE WRONG CODE. |
| | |
| | 3- SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL |
| | CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF |
| | BATHROOM ADDITION. (REPEAT COMMENT). SPECIFY SIZE OF |
| | EXISTING EGRESS WINDOW THAT IS SHOWN NOW AND SIZE OF |
| | EXISTING WINDOW TO BE BLOCKED WITH NEW BATHROOM TO |
| | VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. PLANS |
| | SUBMITTED STILL DON'T SPECIFY THE SIZE OF EXISTING |
| | WINDOW TO REMAIN. EGRESS REQUIREMENTS HAVE BEEN REDUCED |
| | BY ELIMINATING ONE WINDOW. SEE SEC. 501.2 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPTER 472 (REPEAT COMMENT). SURVEYS SUBMITTED ARE |
| | COPIES OF THE SIGNATURE. RESUBMIT SURVEYS WITH ORIGINAL |
| | SIGNATURE. |
| | |