| 2009-05-28 10:30:30 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW THIRD |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD (561)233-5120) TO CHECK IF |
| | IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY |
| | OF PAID RECEIPT. (REPEAT COMMENT. NOT ADDRESSED AT ALL- |
| | THREE TIMES). |
| | |
| | 3- GABLE END DETAIL SHOWN ON SHEET A-3 IS A DETAIL THAT |
| | WAS PASTED TO ORIGINAL DRAWING. REVISE ORIGINAL DRAWING |
| | AS REQUIRED. PASTING TO ORIGINAL DRAWINGS IS NOT |
| | ALLOWED ON SIGNED AND SEALED DRAWINGS. SIGNED AND |
| | SEALED DRAWINGS ARE NOT ALLOWED TO BE ALTERED IN ANY |
| | WAY. |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600 OF 2004 FBC. (NO ENERGY CALCULATIONS WERE |
| | SUBMITTED AT THIS TIME). |
| | |
| | 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF SHINGLES. (REPEAT COMMENT. NOT ADDRESSED AT |
| | ALL. THREE TIMES). |
| | |
| | B) PROVIDE TWO COPIES OF PRODUCT APPROVAL NOA |
| | 05-1018.01 SUBMITTED FOR WINDOWS. ONLY ONE COPY WAS |
| | PROVIDED. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | (REPEAT COMMENT. NOT ADDRESSED AT ALL. THREE TIMES). |
| | |
| | 7- MIN. THICKNESS OF STUCCO ON FRAME CONSTRUCTION IS |
| | 7/8" AS REQUIRED BY SEC. R703.6.4.3 OF 2004 FLORIDA |
| | RESIDENTIAL CODE ( ASTM C926 AND ASTM C-1063). (REPEAT |
| | COMMENT). EXTERIOR ELEVATIONS ON SHEET A-1 SPECIFIES |
| | 5/8" STUCCO THICKNESS. REVISE AS REQUIRED. |
| | |
| | 8- SPECIFY/CLARIFY HOW COMPLYING WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA RESIDENTIAL |
| | CODE IF THE EXISTING WINDOW CAN'T BE USED BECAUSE OF |
| | BATHROOM ADDITION. (REPEAT COMMENT). SPECIFY SIZE OF |
| | EXISTING EGRESS WINDOW THAT IS SHOWN NOW AND SIZE OF |
| | EXISTING WINDOW TO BE BLOCKED WITH NEW BATHROOM TO |
| | VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |