| 2008-12-31 10:41:39 | ** DENIED REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE FS 481.229, 471.003. WHEN MEETING |
| | EXCEPTIONS IN THE STATUTES AS MENTIONED PLANS ARE STILL |
| | REQUIRED TO BE DONE BY THE DESIGN PROFESSIONAL AS |
| | LISTED. |
| | THE PLANS SUBMITTED DO NOT CONTAIN ANY TITLE BLOCKS, |
| | PRINTED NAME, SIGNATURE, OR SIGNED AND SEALED. |
| | |
| | 2) NOTE: PLANS MENTIONS USE OF POSSIBLE EXISTING |
| | LAUNDRY CIRCUIT OR RECEPTACLE CIRCUIT. IT IS NOT |
| | PERMISSIBLE TO USE THE LAUNDRY CIRCUIT. PLEASE SEE |
| | 210.52D, 210.11C2 AND 210.11C3. |
| | THE LAUNDRY CIRCUIT MUST BE SEPARATE AND BE AVAILABLE |
| | FOR LAUNDRY. |
| | THE BATH SHALL BE DEDICATED AS LISTED IN THE ABOVE |
| | SECTIONS. THERE IS TWO SEPARATE WAYS TO WIRE THE |
| | BATHROOMS HOWEVER THE PLANS DO NOT INDICATE COMPLIANCE |
| | WITH EITHER. |
| | MUST BE 20AMP AND #12 WHEN WIRING FOR GFI. |
| | |
| | 2) NOTE: PLANS DO NOT INDICATE ANY NEW ELECTRICAL FOR |
| | PROPOSED A/C SYSTEM. |
| | PLEASE SEE 210.63, 210.8A, 440.11 FOR MISSING GFI |
| | RECEPTACLES, DISCONNECTS ETC |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | THE EXISTING ELECTRICAL SERVICE WITH NEW PROPOSED A/C |
| | LOADS. |
| | PLEASE SEE NEC 220.83. |
| | PLEASE INDICATE THE SIZE OF THE ELECTRICAL SERVICE IN |
| | ORDER TO DETERMINE IF THE EXISTING IS ADEQUATE FOR NEW |
| | LOADS. |
| | 215.5,230.2 |
| | |
| | 4) NOTE: PLEASE SEE FBC 108.3 WHICH REQUIRES THE |
| | APPLIED VALUE TO INCLUDE ALL LABOR, DESIGN COST, |
| | MATERIALS ETC EVEN IF ANY OF THESE ARE OWNER SUPPLIED. |
| | PLEASE SEE VALUATIONS BASED ON THE ADOPTED ICC |
| | STANDARDS APPEARS THIS WILL CHANGE THE VALUE AS |
| | APPLIED. |
| | THE APPLIED SQ FT NOTES 100 SQ FT YET BASED ON THE |
| | PLANS THE SQ FT IS HIGHER. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |