Notes
Date Text
2009-01-08 14:10:42DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT PO.1 DOMESTIC WATER ISOMETRIC SHOWS THE
 DISHWASHER SUPPLY AS COLD WATER. PER SECTION 607.1 HOT
 WATER SHALL BE SUPPLIED TO ALL PLUMBING FIXTURES &
 EQUIPMENT UTILIZED FOR WASHING, CULINARY PURPOSES, &
 CLEANSING.
  
 2. SHT P0.1 DOMESTIC WATER ISOMETRIC WILL BE REQUIRED
 TO SHOW A WATER HAMMER ARRESTOR FOR THE DISHWASHER.
 SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  