Plan Review Notes
Plan Review Notes For Permit 08120457
Permit Number 08120457
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-01-07 12:27:42***PROVISO***
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH THESE AND
 OTHER REVIEW COMMENT CORRECTIONS.
  
 1) PLEASE SHOW THE PROPOSED FIRE SPRINKLER HEAD LAYOUT
 WHICH MAY BE ILLUSTRATED ON THE REFLECTED CEILING PLAN.
 IN ADDITION, SEPARATE SHOP DRAWINGS AND PERMIT WILL BE
 REQUIRED PRIOR TO EQUIPMENT INSTALLATION.
  
 2) FIRE ALARM DRAWINGS SEEM TO SUGGEST CEILING MOUNTED
 A/V DEVICES. PLEASE EXPLAIN AND VERIFY THAT EQUIPMENT
 WILL BE INSTALLED IN ACCORDANCE WITH NFPA 72, 2002.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  