2009-01-24 17:42:17REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NEW MECHANICAL ROOM WILL SERVE AS A RETURN AIR
 PLENUM. SHOW TYPE OF FINISH ON INTERIOR SIDE OF
 EXTERIOR WALLS TO SHOW COMPLIANCE WITH FBCM 603.8 AND
 FBCM 603.9.
  
 2. WHAT TYPE OF DOOR IS LOCATED AT THE ENTRANCE TO THE
 MECHANICAL ROOM? A WOOD DOOR AT THIS LOCATION IS NOT
 PERMISSABLE. MATERIALS EXPOSED WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84
 PER FBCM 602.2.1. ENSURE DOOR AND ALL OTHER MATERIALS
 EXPOSED IN THIS ROOM MEET THIS REQUIREMENT. EXAMPLE:
 DETAIL ON M4 CALLS FOR PVC TO BE USED FOR CONDENSATE
 PIPING. PVC MAY NOT BE LOCATED IN THE PLENUM.
  
 3. PROVIDE AUXILIARY OR SECONDARY DRAIN PROTECTION IN
 ACCORDANCE WITH FBCM 307.2.3.
  
 4. FOR THE OUTDOOR CONDENSING UNIT: MECHANICAL
 APPLIANCES AND THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST WIND PRESSURES AS
 DETERMINED IN ACCORDANCE WITH FBCM 301.13. PROVIDE
 MANUFACTURER'S DATA SHOWING THIS APPLIANCE IS DESIGNED
 FOR WIND RESISTANCE.
  