| Plan Review Notes For Permit 08120454 |
| Permit Number |
08120454 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-24 17:42:17 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. NEW MECHANICAL ROOM WILL SERVE AS A RETURN AIR | | | PLENUM. SHOW TYPE OF FINISH ON INTERIOR SIDE OF | | | EXTERIOR WALLS TO SHOW COMPLIANCE WITH FBCM 603.8 AND | | | FBCM 603.9. | | | | | | 2. WHAT TYPE OF DOOR IS LOCATED AT THE ENTRANCE TO THE | | | MECHANICAL ROOM? A WOOD DOOR AT THIS LOCATION IS NOT | | | PERMISSABLE. MATERIALS EXPOSED WITHIN PLENUMS SHALL BE | | | NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF | | | NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT | | | MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 | | | PER FBCM 602.2.1. ENSURE DOOR AND ALL OTHER MATERIALS | | | EXPOSED IN THIS ROOM MEET THIS REQUIREMENT. EXAMPLE: | | | DETAIL ON M4 CALLS FOR PVC TO BE USED FOR CONDENSATE | | | PIPING. PVC MAY NOT BE LOCATED IN THE PLENUM. | | | | | | 3. PROVIDE AUXILIARY OR SECONDARY DRAIN PROTECTION IN | | | ACCORDANCE WITH FBCM 307.2.3. | | | | | | 4. FOR THE OUTDOOR CONDENSING UNIT: MECHANICAL | | | APPLIANCES AND THAT ARE EXPOSED TO WIND SHALL BE | | | DESIGNED AND INSTALLED TO RESIST WIND PRESSURES AS | | | DETERMINED IN ACCORDANCE WITH FBCM 301.13. PROVIDE | | | MANUFACTURER'S DATA SHOWING THIS APPLIANCE IS DESIGNED | | | FOR WIND RESISTANCE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|