| 2008-12-26 16:23:23 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS FOR NEW AND EXISTING. BEFORE GRANTING |
| | ADDITIONAL LIGHTING , THE EXISTING NEEDS TO BE |
| | VERIFIED. |
| | |
| | 2) NOTE: PLEASE ELABORATE NOTE ON PLANS WITH RESPECT TO |
| | IT/TELCO ROOM DESIGNATION. IF THIS IS NOT AN IT ROOM AS |
| | DEFINED IN NEC 645.2. PLEASE BE SURE TO ADD TO NOTE |
| | WHICH WILL STATE *** NO WIRING METHODS IN NEC 645 IS |
| | PERMITTED**. |
| | CONFIRMATION OF COUNTY IT/MIS STAFF MAY BE NEEDED TO |
| | CONFIRM NO WIRING METHODS PERMITTED IN 645 IS DESIRED. |
| | IF THIS IS NOT AN IT ROOM, ALL WIRING SHALL BE IN |
| | ACCORDANCE WITH CHAPTERS 1-4. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |