2009-01-09 10:20:18***PROVISO***
  
 1) FA0.1 NOTE #17 SHOULD READ SMOKE DUCT DETECTORS TO
 INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 2) CEILING MOUNTED FIRE ALARM EQUIPMENT SHALL COMPLY
 WITH THE REQUIREMENTS OF NFPA 72, 2002.
  
 3) ACCESS CONTROLLED EGRESS DOORS TO COMPLY WITH NFPA
 101, SEC. 7.2.1.6.2. IN ADDITION, SEPARATE SHOP
 DRAWINGS AND PERMIT REQUIRED PRIOR TO EQUIPMENT
 INSTALLATION.
  
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH THESE COMMENTS
 ADDRESSED.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW