| Plan Review Notes For Permit 08120430 |
| Permit Number |
08120430 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-09 10:20:18 | ***PROVISO*** | | | | | | 1) FA0.1 NOTE #17 SHOULD READ SMOKE DUCT DETECTORS TO | | | INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | 2) CEILING MOUNTED FIRE ALARM EQUIPMENT SHALL COMPLY | | | WITH THE REQUIREMENTS OF NFPA 72, 2002. | | | | | | 3) ACCESS CONTROLLED EGRESS DOORS TO COMPLY WITH NFPA | | | 101, SEC. 7.2.1.6.2. IN ADDITION, SEPARATE SHOP | | | DRAWINGS AND PERMIT REQUIRED PRIOR TO EQUIPMENT | | | INSTALLATION. | | | | | | | | | PLANS WILL BE STAMPED WHEN RETURNED WITH THESE COMMENTS | | | ADDRESSED. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|