| 2008-12-30 13:37:24 | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC |
| | 13-101.1,13-101.1.3,13-400.0.C.4 ETC |
| | PLEASE SEE THE SUBMITTED LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2,13-415.2.ABC.1.1, .1.2. |
| | PLEASE SEE TABLE 13-415.2.B. |
| | THE TOTAL SHOWN FOR ROOM/AREA 118 FOR EXAMPLE SEEMS TO |
| | BE OVER THE MAXIMUM ALLOWANCES. |
| | PLEASE ALSO SEE AREAS SUCH AS LOUNGE 121 WHICH |
| | INDICATES THE DESIGN WATTAGE AS 294. |
| | BASED ON THE WATTAGE OF FIXTURES AND THE NUMBER OF |
| | FIXTURES ON PLANS FOR THIS SPACE THIS DOES NOT |
| | COORDINATE.. |
| | |
| | 2) NOTE: PLEASE INDICATE ANY NIGHT LIGHTS. NONE SHOWN |
| | ON PLANS. |
| | 13-415.1.ABC.1. |
| | |
| | 3) NOTE: PLEASE OBTAIN THE LATEST UPDATED RISER |
| | DIAGRAM. THE RISER DIAGRAM AS SUBMITTED DOES NOT |
| | CONTAIN ALL ELECTRICAL AS ALREADY EXISTING ON SITE. |
| | 215.5, 230, 240 ETC |
| | FBC 106.1.1 FOR CLARITY, ADDITIONAL INFORMATION AND |
| | COORDINATION OF PLANS. |
| | |
| | 4) NOTE: SHEET E2.1 MAKES NOTE TO SEE SHEET 5.1 FOR |
| | PART ROOM LAYOUT FOR ELECTRICAL EQUIPMENT ETC HOWEVER |
| | NO ROOM LAYOUT IS SHOWN ON E5.1. (RISER SHEET). |
| | |
| | 5) NOTE: PLEASE SHOW ALL DEVICE LOCATIONS, HEIGHTS AND |
| | LEVELS PER FBC 11-4.28,.1,.2 AND .3 FOR FIRE ALARM |
| | DEVICES, PULL STATIONS, HORNS, STROBES ETC. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |