Plan Review Notes
Plan Review Notes For Permit 08120430
Permit Number 08120430
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-30 13:37:24** DENIED REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE FBC
 13-101.1,13-101.1.3,13-400.0.C.4 ETC
 PLEASE SEE THE SUBMITTED LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2,13-415.2.ABC.1.1, .1.2.
 PLEASE SEE TABLE 13-415.2.B.
 THE TOTAL SHOWN FOR ROOM/AREA 118 FOR EXAMPLE SEEMS TO
 BE OVER THE MAXIMUM ALLOWANCES.
 PLEASE ALSO SEE AREAS SUCH AS LOUNGE 121 WHICH
 INDICATES THE DESIGN WATTAGE AS 294.
 BASED ON THE WATTAGE OF FIXTURES AND THE NUMBER OF
 FIXTURES ON PLANS FOR THIS SPACE THIS DOES NOT
 COORDINATE..
  
 2) NOTE: PLEASE INDICATE ANY NIGHT LIGHTS. NONE SHOWN
 ON PLANS.
 13-415.1.ABC.1.
  
 3) NOTE: PLEASE OBTAIN THE LATEST UPDATED RISER
 DIAGRAM. THE RISER DIAGRAM AS SUBMITTED DOES NOT
 CONTAIN ALL ELECTRICAL AS ALREADY EXISTING ON SITE.
 215.5, 230, 240 ETC
 FBC 106.1.1 FOR CLARITY, ADDITIONAL INFORMATION AND
 COORDINATION OF PLANS.
  
 4) NOTE: SHEET E2.1 MAKES NOTE TO SEE SHEET 5.1 FOR
 PART ROOM LAYOUT FOR ELECTRICAL EQUIPMENT ETC HOWEVER
 NO ROOM LAYOUT IS SHOWN ON E5.1. (RISER SHEET).
  
 5) NOTE: PLEASE SHOW ALL DEVICE LOCATIONS, HEIGHTS AND
 LEVELS PER FBC 11-4.28,.1,.2 AND .3 FOR FIRE ALARM
 DEVICES, PULL STATIONS, HORNS, STROBES ETC.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  