| Date |
Text |
| 2009-03-25 14:56:40 | PLANS ROUTED TO DOUG WISE'S OFFICE. THERE IS A NEW C-3 |
| | WHICH PREVIOUSLY HAD ZONING AND ENGINEERING STAMPS. |
| 2009-03-25 14:55:48 | |
| | **** PROVISO *** |
| | |
| | ** THIS PROVISO HAS BEEN ISSUED TO PROJECT WITH THE |
| | FOLLOWING CONDITIONS. ALL ITEMS IN NOTES BELOW MUST BE |
| | SUBMITTED, REVIEWED AND STAMPED WITH A PASSED STATUS |
| | BEFORE INSTALLATION OF ELECTRICAL EQUIPMENT OR |
| | INSPECTIONS. |
| | ANY INSTALLATION OF EQUIPMENT OR INSPECTIONS IN WHICH |
| | THE NOTES HAVE NOT BEEN ADDRESSED MAY CREATE A DELAY IN |
| | THE PROJECT OR REMOVAL OF INSTALLED EQUIPMENT. THIS |
| | WOULD BE AT THE SOLE RESPONSIBILITY AND EXPENSE OF THE |
| | CONTRACTORS INVOLVED WITH PROJECT. |
| | |
| | 1) NOTE: THIS IS THE *THIRD* REQUEST FOR THE |
| | MANUFACTURES SPECS/CUT SHEETS ON THE TWO PROPOSED MTS |
| | PANELS/DEVICES AS SHOWN ON RISER. THE POWER PROTECTION |
| | SPECS WERE SUBMITTED WITH LISTING AS UL 891. THIS DOES |
| | NOT PROVIDE ANY INFORMATION FOR LISTING OF TRANSFER |
| | EQUIPMENT. |
| | THERE ARE NO SUBMITTALS IN PACKAGE FOR ANY OF THE OTHER |
| | EQUIPMENT AS REQUESTED. THERE IS HOWEVER SPECS FOR THE |
| | METER CENTER AND OTHER EQUIPMENT WHICH WAS NEVER |
| | REQUESTED ON ANY OF THE PREVIOUS REVIEWS. |
| | 702.6, 701.7, 110.3, 90.7 ETC |
| | |
| | 2) NOTE: THE LIGHTING DETAILS ON SHEET E-9 WAS NOT |
| | REVISED TO SHOW LIGHTING BEING FED TO NEW HOUSE PANEL |
| | AT THE EQUIPMENT/STRUCTURE LOCATION. NO LIGHTING SHALL |
| | BE FED FROM HOUSE PANEL AT OFFICE BUILDING. |
| | THE OVER CURRENT PROTECTION AND CONDUCTORS SHOWN ON E-9 |
| | ARE ALSO NOT THE SAME AS THE NEW ON E-9. PLEASE |
| | COORDINATE AND REVISE ALL AS NEEDED. |
| | AS REQUESTED ON PREVIOUS REVIEWS. PLEASE SHOW LOCATIONS |
| | OF ALL LIGHTING FIXTURES. PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND BE SURE THIS INFORMATION IS COORDINATED WITH |
| | PANEL SCHEDULES. |
| | 408.4, 310.16, 240.4 ETC |
| | |
| | 3) NOTE: PLEASE BE SURE TO INDICATE THE AIC RATINGS FOR |
| | ALL EQUIPMENT ON THE RISER/PLANS. ALL EQUIPMENT SHALL |
| | BE RATED FOR THE AVAILABLE FAULT CURRENT WHETHER FROM |
| | THE UTILITY TRANSFORMER OR ANY FUTURE GENERATORS. 110.9 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION AS A REVISION |
| | BEFORE INSPECTIONS AND INSTALLATION. |
| | IF THERE ARE ANY QUESTIONS OR IF ANY OF ABOVE COMMENTS |
| | ARE NOT TYPED IN A CLEAR MANNER, PLEASE DO NOT HESITATE |
| | IN CONTACTING THIS REVIEWER. |
| | |