| 2009-03-13 11:09:57 | ** DENIED RE-SUB ** |
| | |
| | |
| | 1) NOTE: PER COMMENTS ON THE PREVIOUS REVIEW. PLEASE |
| | ADJUST THE VALUE FOR THE COMPLETE SCOPE OF WORK |
| | INCLUDING, DESIGN FEES, ALL LABOR, ALL MATERIALS AND |
| | ALL EQUIPMENT WHETHER OR NOT ANY OF THESE ITEMS ARE |
| | OWNER SUPPLIED AND NOT PROVIDED BY THE CONTRACTOR. |
| | SCOPE OF WORK ON PROJECT INCLUDES 100FT FLAG POLE |
| | TOWER, BASE, ALL ELECTRICAL EQUIPMENT FOR SERVICE, |
| | CABINETS, FOUNDATION, WALLS AND FOUNDATION FOR WALLS, |
| | ELECTRICAL SERVICE FROM FPL ETC. |
| | THE ADJUSTED VALUE FROM $80K, TO $125K IS STILL LOW. AS |
| | MENTIONED PREVIOUSLY ALL EQUIPMENT, LABOR, MATERIALS, |
| | DESIGN COST ETC SHALL BE INCLUDED. |
| | VALUE CAN BE ASSESSED USING THE ADOPTED GUIDES AND |
| | VALUES PUBLISHED. |
| | FBC 108.3 |
| | |
| | 2) NOTE: PLEASE INCLUDE THE EQUIPMENT MANUFACTURES |
| | SPECS/CUT SHEETS FOR THE TRANSFER EQUIPMENT. SOME |
| | MANUFACTURES EQUIPMENT SPECS/CUT SHEETS WERE SUBMITTED |
| | HOWEVER NOTHING SPECIFIC TO THE TRANSFER EQUIPMENT AND |
| | ANY 1008 LISTING. |
| | 90.7, 110.3, 701.7 |
| | |
| | 3) NOTE: PLEASE PROVIDE INFORMATION ON THE CIRCUITING |
| | AND INFORMATION ON LIGHTING FIXTURES ON THIS STRUCTURE |
| | WHICH IS NOT PART OF THE BASE BUILDING. THE PLANS ONLY |
| | NOTE AN EXISTING HOUSE PANEL. |
| | NO, GROUNDING INFORMATION ON CIRCUITING FOR THESE |
| | FIXTURES, NO DISCONNECTING MEANS, AND NO FIXTURE |
| | INFORMATION. WHERE IS CIRCUITING, LOADS ETC IS |
| | PROVIDED. |
| | IF THIS IS LEGALLY LEASED SPACE THE LIGHTING FIXTURES |
| | NEED TO COME FROM THIS SERVICE AND EQUIPMENT. PLANS |
| | HAVE A WHOLE NEW SERVICE AND TRANSFORMER WHICH IS A |
| | SEPARATELY DERIVED SYSTEM. IF THIS IS ONE STRUCTURE |
| | BEING FED FROM TWO COMPLETELY DIFFERENT SERVICES THEN |
| | BONDING OF SERVICES, GROUPING OF MAINS/DISCONNECTING |
| | MEANS ETC NEEDS TO BE ADDRESSED. THERE IS A WAY TO |
| | ADDRESS THIS HOWEVER PLEASE CALL TO GO OVER. |
| | 250.50,250.20,250.32,225.31-225.39,220,408.4, 310.16, |
| | 240.4 ETC. |
| | THIS CAME UP IN A PREVIOUS CONVERSATION WITH DESIGNER |
| | EVEN AS IT WAS NOT SPECIFICALLY GONE OVER IN PREVIOUS |
| | COMMENTS. |
| | |
| | 4) NOTE: TITLE SHEET DOES LIST AN E-1 TO BE IN SET |
| | HOWEVER NOT E-1 IS IN EITHER SET. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |