| 2009-03-31 10:31:06 | BUILDING PLAN REVIEW |
| | PERMIT: 08120369 |
| | ADD: 100 N CLEMATIS ST |
| | CONT: CATALFUMO |
| | TEL: (561)282-8265 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | APRIL 1/ 2009 |
| | |
| | ARCHITECT: STEPHEN BORUFF |
| | STEPHEN L. BORUFF, AIA |
| | ARCHITECTS+ PLANNERS, INC. |
| | |
| | STRUCTURAL ENGINEER: TOLLIVER J. FRAZIER |
| | ONM&J STRUCTURAL ENGINEERS |
| | |
| | |
| | BUILDING PROVISO: |
| | |
| | |
| | 1) ROOFING SYSTEMS: |
| | ROOF INSULATION REVIEW THE MINIMUM THICKNESS FOR A 20.4 |
| | R-VALUE SEE ENERGY INPUT DATA REPORT |
| | PRODUCT APPROVAL NOA 07-0228.04 |
| | DECK TYPE 21: STEEL INSULATED |
| | DECK DESCRIPTION 18-22 GAUGE TYPE B |
| | SYSTEM TYPE B(1) |
| | MAXIMUM DESIGN PRESSURE -75 PSF LIMITATION # 7 ALLOWS |
| | FOR ENHANCED FASTENING S-4 FOR THE ROOF ZONE 3 REQUIRES |
| | -107. |
| | THE RAS 117 CALCULATIONS CAN BE COMPLETED BY EITHER A |
| | ARCHITECT, ENGINEER OR REGISTEERED ROOF CONSULTANT. |
| | |
| | ARCHITECT RESPONSE: ROOFING SHOP DRAWING/ PRODUCT |
| | SUBMITTAL SHALL INCLUDE FASTENER CALCULATIONS. |
| | FASTENER CALCULATIONS ARE TO BE SUBMITTED AS PART OF |
| | THE ROOFING PERMIT UNDER SEPERATE REVIEW. |
| | |
| | 2) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF |
| | ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN |
| | "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE |
| | REQUIRED BEFORE A CERTIFICATE OF OCCUPANCY WILL BE |
| | ISSUED. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |