| 2009-02-17 15:12:36 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | THIS COMMENT WAS FROM THE PREVIOUS REVIEW |
| | |
| | 17} PER 13-415.2.ABC.1.1. PAGE #2 OF THE ENERGY GAUGE |
| | INPUT DATA REPORT, DOES NOT INDICATE THE CORRECT NUMBER |
| | OF FIXTURES AS SHOWN ON THE PLAN, THE WATTAGES PER |
| | LUMINAIRE ARE INCORRECT, AND THE CONTROL TYPE MUST BE |
| | PER 13-415.1ABC.1.2. NO LIGHTING POWER DENSITIES PER |
| | 13-415, INTERIOR OR EXTERIOR WERE GIVEN. COMPLY WITH |
| | CHAPTER 13 FBC.***THE EXTERIOR AND INTERIOR WATTAGES |
| | AND COUNTS DO NOT CORRELATE WITH THE LIGHTING FIXTURE |
| | SCHEDULE ON SHEET VC E-11.0. |
| | |
| | NEW COMMENT, SHEET VC E-5.0 |
| | |
| | 1} THE NOTE REGARDING THE FIXTURES TO BE DETERMINED AT |
| | A LATER DATE IS NOT ACCEPTABLE. A SYSTEM MUST BE SHOWN |
| | THAT MEETS THE REQUIREMENTS OF THE CODE. IT MAY BE |
| | REVISED AT A LATTER DATE. ALSO SEE 13-415.2.ABC.1.2 -3. |
| | THE WATTAGE OF LINE-VOLTAGE LIGHTING TRACK AND PLUG-IN |
| | BUSWAY THAT ALLOW THE ADDITION AND/OR RELOCATION OF |
| | LUMINAIRES WITHOUT ALTERING THE WIRING OF THE SYSTEM |
| | SHALL BE THE SPECIFIED WATTAGE OF THE LUMINARIES |
| | INCLUDED IN THE SYSTEM WITH A MINIMUM OF 30 WATTS PER |
| | LINEAR FOOT. |
| | |
| | 2} SHEET VC E-10.0 AND AC-1 LOCATE THE AHU'S IN |
| | DIFFERENT SPACES IN THE ELECTRICAL ROOM. CORRELATE THE |
| | SHEETS AND SEE 110.26(F)(1)(B) 2005 NEC FOR FOREIGN |
| | SYSTEMS IN DEDICATED SPACE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |