| 2009-01-24 16:58:46 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE COMPLETE SUBMITTALS OF PRODUCT APPROVALS FOR |
| | LOUVERS TO BE USED ON THIS PROJECT, INCLUDING |
| | INSTALLATION DETAILS. ENSURE PRODUCT APPROVALS ARE |
| | CURRENT IN ACCORDANCE WITH FAC RULE 9B-72. PRODUCT |
| | APPROVALS ARE TO BE APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD IN ACCORDANCE WITH FBCB 106.3.3. |
| | |
| | 2. NOTE #13 ON AC-1 CALLS FOR CONDENSATE TO DISCHARGE |
| | IN PLANTERS. CONDENSATE LINES SHALL DISCHARGE AT LEAST |
| | 1 FOOT AWAY FROM THE STRUCTURE SIDEWALL IN ACCORDANCE |
| | WITH FBCB 1503.6. |
| | |
| | 3. ARCHITECTURAL DOOR SCHEDULE CALLS FOR MECHANICAL |
| | ROOM 105 DOOR TO BE ???FRP.??? DOES THIS REPRESENT |
| | FIBERGLASS REINFORCED PLASTIC? MATERIALS EXPOSED WITHIN |
| | PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME |
| | SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED |
| | INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 84 PER FBCM 602.2.1. PROVIDE A |
| | NONCOMBUSTIBLE DOOR AT THIS LOCATION OR PROVIDE ASTM |
| | E84 DATA FOR THE SPECIFIED DOOR. |
| | |
| | 4. PROVIDE SHUTOFF DAMPER CONTROLS FOR THE AHU1 OUTSIDE |
| | AIR INTAKE IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3. |
| | |
| | 5. FOR OUTDOOR CONDENSING UNITS: APPLIANCES AND |
| | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| | INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT |
| | AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM |
| | 301.13. PROVIDE MANUFACTURERS DATA SHOWING THESE |
| | CONDENSING UNITS DESIGNED FOR WIND RESISTANCE. |
| | |
| | 6. PROVIDE CONFIRMATION THAT THE CONDENSING UNITS ARE |
| | TO BE INSTALLED ABOVE BASE FLOOD ELEVATION IN |
| | ACCORDANCE WITH FBCM 301.14. |
| | |
| | 7. PROVIDE ADEQUATE DOCUMENTATION FOR ROOFING SYSTEM TO |
| | BE USED, CONFIRMING THAT MINIMUM R-20 INSULATION SHALL |
| | BE PROVIDED ABOVE MECHANICAL ROOM 105 AS REQUIRED BY |
| | THE MECHANICAL SPECIFICATIONS. |
| | NOTE: MINIMUM R-19 IS REQUIRED IN ACCORDANCE WITH FBCB |
| | 13-404.1.ABC.2. |
| | |
| | 8. SHOW HOW WALLS OF MECHANICAL ROOM 105 ARE TO BE |
| | FINISHED IN ACCORDANCE WITH FBCM 603.8 AND 603.9. |
| | |
| | 9. ALTHOUGH THE DOOR SCHEDULE CALLS FOR GASKETED FRAME |
| | AND THRESHOLD, IT IS STRONGLY RECOMMENDED THAT A DUCTED |
| | RETURN AND OUTSIDE AIR BE PROVIDED IN MECHANICAL ROOM |
| | 105 TO AVOID ANY INCIDENTAL RECIRCULATION OF AIR FROM |
| | THE MENS RESTROOM AREA INTO THE CONDITIONED VISITOR |
| | CENTER AREAS. THIS CHANGE WOULD ALSO NEGATE SOME OF THE |
| | REVIEW COMMENTS LISTED ABOVE. RECIRCULATION OF AIR FROM |
| | THIS AREA IS PROHIBITED IN ACCORDANCE WITH FBCM |
| | 403.2.1. |
| | |