| 2009-08-12 09:51:36 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1-4. ADDRESSED. |
| | |
| | 5. IMPACT FEES REQUIRED, 561-233-5025 (ADDITION OF 166 |
| | SF). PLANS ARE TO BE STAMPED AND RECEIPT PROVIDED. THIS |
| | CAN BE DONE LAST; AFTER ALL REVIEWS BUT BEFORE PERMIT |
| | IS ISSUED. IMPACT FEE ASSESSMENT IS REQUIRED WHEN A |
| | SCREENED PORCH IS CONVERTED TO ENCLOSED SPACE. |
| | |
| | 6. ADDRESSED. |
| | |
| | 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | THE SLIDING GLASS DOOR. FAC9B72. |
| | |
| | RESPONSE LETTER STATES THAT THIS IS ENCLOSED, BUT I WAS |
| | UNABLE TO FIND THIS IN THE PACKAGE. THE NEW PLAN SHOWS |
| | SLIDERS AND FIXED GLASS. PRODUCT APPROVALS ARE REQUIRED |
| | FOR THE FIXED GLASS, SLIDERS, AND MULLIONS. |
| | |
| | 8. INSTALLATION SCHEDULE (SHUTTERS): |
| | A. PLEASE EXPLAIN HOW A 104" HIGH OPENING WITH A 2.5" |
| | EDGE DISTANCE, WALL CONNECTION, CAN HAVE A 8' SPAN. IT |
| | APPEARS THAT THE SPAN SHOULD BE A MINIMUM OF 9'1". |
| | B. SEE SHEET 4, CONCRETE IS TO BE A MINIMUM OF 3320PSI; |
| | PATIO SLABS ARE USUALLY 2500PSI. CONCRETE BLOCK ANCHOR |
| | SPACING MAY BE USED IF YOU CANNOT DEMONSTRATE PROOF OF |
| | MINIMUM CONCRETE STRENGTH. |
| | |
| | 9. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 505.1. |
| | |
| | THE SLIDING GLASS DOOR, ACCORDING TO THE PLANS |
| | PROVIDED, APPEARS TO SERVE AS THE ONLY EMERGENCY MEANS |
| | OF ESCAPE FOR THE BEDROOM. THE BUILDING IS NOT TO BE |
| | ALTERED TO MAKE THE BUILDING LESS SAFE, FBC R501.2. IS |
| | THIS A FULLY SPRINKLERED BUILDING? PLEASE EXPLAIN |
| | RATIONALE FOR BLOCKING WHAT APPEARS TO BE THIS |
| | BEDROOM'S ONLY EMERGENCY EGRESS. |
| | |
| | 3RD REVIEW, PLANS SHOW AN ENCLOSED PATIO WITH SLIDING |
| | GLASS DOORS BETWEEN BEDROOM EMERGENCY ESCAPE AND THE |
| | OUTDOORS. EMERGENCY ESCAPE IS TO OPEN DIRECTLY TO THE |
| | OUTDOORS. PLEASE CONTACT ME IF YOU WISH TO DISCUSS. |
| | |
| | 10-16. ADDRESSED. |
| | |
| | |