| 2009-01-29 15:18:09 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1-4. ADDRESSED. |
| | |
| | 5. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY, |
| | 561-233-5025 (ADDITION OF 166 SF). AS SCOPE IS NOT |
| | CLEAR, IMPACT FEE REQUIREMENT IS NOT CLEAR. |
| | |
| | 2ND REVIEW, PLEASE HAVE PLANS STAMPED AND RECEIPT, IF |
| | FEES DUE, PROVIDED. 233-5025. THIS PERMIT CONVERTS A |
| | PORCH TO INTERIOR SPACE. IMPACT FEES MAY BE DUE. |
| | |
| | 6. ADDRESSED. |
| | |
| | 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | THE SLIDING GLASS DOOR. FAC9B72. |
| | |
| | PLEASE HAVE THE PRODUCT APPROVALS REVIEWED BY DESIGNER |
| | OF RECORD, FBC*106. |
| | |
| | 8. FOR THE SHUTTERS, COMPLETE THE ATTACHED INSTALLATION |
| | SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE |
| | COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301, |
| | FBC1609. TWO SETS REQUIRED. |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | 9. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 505.1. |
| | |
| | THE SLIDING GLASS DOOR, ACCORDING TO THE PLANS |
| | PROVIDED, APPEARS TO SERVE AS THE ONLY EMERGENCY MEANS |
| | OF ESCAPE FOR THE BEDROOM. THE BUILDING IS NOT TO BE |
| | ALTERED TO MAKE THE BUILDING LESS SAFE, FBC R501.2. IS |
| | THIS A FULLY SPRINKLERED BUILDING? PLEASE EXPLAIN |
| | RATIONALE FOR BLOCKING WHAT APPEARS TO BE THIS |
| | BEDROOM???S ONLY EMERGENCY EGRESS. |
| | |
| | 10. ADDRESSED. |
| | |
| | 11. PROVIDE A SITE PLAN SHOWING PROPOSED IMPROVEMENT |
| | AND DISTANCE TO ALL PROPERTY LINES. |
| | |
| | NOT ADDRESSED. IT APPEARS THAT THE ADJACENT UNIT IS |
| | 3FT6IN FROM THE PROPERTY LINE. PLEASE PROVIDE A SITE |
| | PLAN WHICH SHOWS THE DIMENSION OF THIS BUILDING FROM |
| | THE PROPERTY LINE, FBCR302. |
| | |
| | NEW COMMENTS: |
| | |
| | 13. FBC1714.5.3.3.1, WINDOW ASSEMBLIES ARE TO BE |
| | TESTED. |
| | |
| | 14. THE SHUTTER INSTALLATION SCHEDULE SHOWS ONE |
| | OPENING. THE ENTIRE WALL IS GLASS. PLEASE REVISE TO |
| | INCLUDE ALL OPENINGS. |
| | |
| | 15. INSTALLATION SCHEDULE, SHUTTER CONNECTION MOUNTING |
| | TYPE, SHOULD CORRELATE WITH THE PRODUCT APPROVAL ANCHOR |
| | CHARTS; IN THIS CASE, C1 THROUGH C4. THIS INFORMATION |
| | IS REQUIRED TO COMPLETE THE REVIEW. |
| | |
| | 16. FEES HAVE BEEN ADJUSTED BASED ON REVISED VALUE. |
| | PLEASE PAY AT THIS TIME. |
| | |
| | A SET HAS BEEN RETAINED. WHEN RESUBMITTING, PLEASE |
| | SUBMIT TWO ORIGINAL SIGNED AND SEALED SETS. |
| | |
| | |