| 2009-01-28 13:40:39 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT A-1 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___LAV: |
| | A. 11-4.19.2 CLEARANCE (29" REQD) |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | |
| | 2. SHT A-1 SHOW THE WATER CLOSET 1'6" OFF THE WALL TO |
| | THE CENTERLINE OF THE FIXTURE. CHAPTER 11 FIGURE 28. -- |
| | SHOW THE LAV MINIMUM 15" OFF THE WALL TO THE CENTERLINE |
| | OF THE FIXTURE. (FIXTURE SHALL BE CENTERED ON THE 30" |
| | MEASUREMENT OF THE 30"X48" CLEAR FLOOR SPACE). |
| | |
| | 3. SHT A-1 TOILET ROOM. PLEASE INDICATE THE LENGTH AND |
| | WIDTH DIMENSIONS OF THE TOILET ROOM AND INDICATE |
| | COMPLIANCE WITH THE FINISH REQUIREMENTS PER SECTIONS |
| | 1210.1 & 1210.2. FLOOR REQUIREMENTS & WALLS WITHIN 2 |
| | FEET OF THE WATER CLOSET SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE. SECTION 106.1.2. |
| | |
| | 4. SHT MEP-1 PLUMBING NOTES, CODE CRITERIA INDICATES |
| | COMPLIANCE WITH THE STANDARD PLUMBING CODE. THE CODE |
| | ADOPTED IS THE FBC-2004 PLUMBING CODE WITH 2007 |
| | AMENDMENTS. PLEASE INDICATE ON PLANS. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |