| Plan Review Notes For Permit 08120340 |
| Permit Number |
08120340 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-24 17:14:20 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THIS SPACE WAS ORIGINALLY DESIGNED AS A RESIDENTIAL | | | (R2) OCCUPANCY. SHOW HOW THE REQUIRED RATE OF | | | VENTILATION IS TO BE PROVIDED FOR THE NEW PROPOSED USE | | | AND RECONFIGURED SPACES IN ACCORDANCE WITH FBCEB 809.1 | | | AND FBCM 403.3. ADDITIONAL COOLING LOADS ON EXISTING | | | EQUIPMENT MAY REQUIRE A RECALCULATION OF COOLING LOADS | | | IN ACCORDANCE WITH THESE SECTIONS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|