| Date |
Text |
| 2008-12-26 17:02:51 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| | ARE LISTED ON ELECTRICAL PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | COORDINATE WITH THE SUBMITTED PANEL SCHEDULE. |
| | 240.4,310.16, 408.4 |
| | FBC 106.1.1,106.1.2, 106.3.5.1.2, 106.5. CLARITY, |
| | COORDINATION AND ADDITIONAL INFORMATION OF RECORD |
| | PLANS. |
| | |
| | 3) NOTE: PLEASE OBTAIN MORE INFORMATION ON THE BASE |
| | BUILDING ELECTRICAL SERVICE WHICH FEEDS THIS TENANT |
| | SPACE. |
| | THE SERVICE RISER AS SHOWN IS NOT ENTIRELY ACCURATE. |
| | THIS SPACE IS NOT FED BY A SEPARATE SERVICE FROM FPL. |
| | PLEASE REVISE RISER. |
| | 230,225,215.5 ETC |
| | |
| | 4) NOTE: PLEASE KNOW THAT ALL CONDUITS, CONDUCTORS |
| | AFTER THE FIRST MEANS OF DISCONNECT IS REQUIRED TO |
| | CONTAIN EQUIPMENT GROUNDING CONDUCTORS. 250.6,250.24 |
| | ETC. THE METER AS SHOWN IS TENANT METER AND IS REQUIRED |
| | TO CONTAIN A FLOATING NEUTRAL. |
| | |
| | 5) NOTE: PLEASE SEE NEC 517.1 FOR HEALTH CARE. THIS IS |
| | NOW SHOWN AS A DOCTOR?S OFFICE USED FOR EXAMS WHICH IS |
| | REQUIRED TO MEET 517 PART II. PLEASE SEE 517.10 AND |
| | REVISE ALL WIRING AS REQUIRED. |
| | PLEASE KNOW BASED ON A MIXED OCCUPANCY AS SUBMITTED THE |
| | WIRING METHODS IN THE MEDICAL/EXAM OFFICES SHALL MEET |
| | 517 AS NOTED. |
| | |
| | 6) NOTE: PLEASE SUBMIT LOAD CALCULATIONS IN ACCORDANCE |
| | WITH NEC 220. PLEASE SEE 220.112,220.14, 220.42, |
| | 220.43, 220.44 ETC. |
| | PLEASE SEE 215.3,230.42 FOR ALL CONTINUOUS LOADS WHICH |
| | ARE REQUIRED TO BE SHOWN AT 125% AND 422.13 FOR |
| | ELECTRICAL STORAGE TYPE WATER HEATERS. |
| | THE LOAD CALCULATIONS AS SUBMITTED ARE FOR A |
| | RESIDENTIAL UNIT ONLY. |
| | |
| | 7) NOTE: PLEASE SEE 600.5 FOR REQUIRED SIGN CIRCUIT. |
| | PLEASE SURE THE MINIMUM VA REQUIRED FOR THE SIGN |
| | CIRCUIT AT A CONTINUOUS LOAD RATING IS FIGURED INTO THE |
| | CALCULATIONS. |
| | (1200VA AT 125%). |
| | |
| | 8) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3 |
| | AND .1.4 FOR MINIMUM REQUIRED LIGHTING CONTROLS FOR NEW |
| | INSTALLED. |
| | PLEASE SEE 13-415.1.ABC.1. THIS IS A TENANT SPACE IN A |
| | BUILDING GREATER THAN 5K SQ FT. |
| | |
| | 9) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE LEVELS |
| | CALCULATIONS FOR NEW BUSINESS AREAS. PLEASE BE SURE TO |
| | SEE 13-415.2, 13-415.2.ABC.1.1,.1.2. |
| | PLEASE BE SURE TO SUBMIT A FIXTURE LEGEND FOR ALL NEW |
| | FIXTURES AND PLEASE BE SURE ALL WATTAGES ETC ARE SHOWN. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |