| Plan Review Notes For Permit 08120335 |
| Permit Number |
08120335 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-12 14:00:00 | BUILDING REVIEW COMMENTS | | | | | | | | | ENGINEERING DESIGN FOR THE TOWER RENOVATIONS SHALL | | | COMPLY WITH ASCE 7-02 REQUIRING A MINIMUM BASIC WIND | | | SPEED OF 140MPH. SEE 2004 FBC, SECTION 1609.1.1, | | | EXCEPTION #7. | | | | | | PLEASE PROVIDE REVISED SIGNED AND SEALED ENGINEERED | | | ANALYSIS. | | | | | | | | | | | | | | | | | | | | | LUIS MARTINEZ | | | 561-805-6710 |
|