| Plan Review Notes For Permit 08120332 |
| Permit Number |
08120332 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-18 07:17:45 | | | | | | | | | | PASSED/PROVISO | | | | | | REVISION REQUIRED | | | | | | THE PIPING SHALL BE A MINIMUM 2-1/2" FOR THE SECTIONS | | | OF PIPE BETWEEN P24G AND P23G ON LINE 1 AND THE | | | STUB-OUT AND SHUT OFF VALVE SHALL BE 1" FOR THE FIRST | | | P17G ON LINE ONE PER TABLE 402.4(1). -- MANUF. ITEM 24 | | | ANETS GOLDEN GRILL CHROME GAS GRILLS DOES NOT REFLECT | | | THE BTU LOAD INDICATED ON THE RISER DIAGRAM. THE 72,000 | | | BTU IS INDICATED AS "LP" BTUH ON THE MANUF. | | | SPECIFICATION SHEETS. (MANUF. ITEM 24.1 IS APPROVED FOR | | | THE IMPERIAL SNAP ACTION GRIDDLES AS P24G). PLEASE | | | CLARIFY. |
|