Plan Review Notes
Plan Review Notes For Permit 08120329
Permit Number 08120329
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-12-23 15:32:10PLANS APPROVED AND STAMPED ON THIS DATE.
  
 1) TWO (2) HOUR HYDROSTATIC TEST REQUIRED PER NFPA 13,
 2002.
  
 2) FIRE SPRINKLER PIPE INSPECTION REQUIRED. CODE 603
  
 3) FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED WITH
 KNOX LOCKING CAPS PRIOR TO FINAL INSPECTION.
  
 4) IN ADDITION TO ELECTRONIC SUPERVISION, DOUBLE CHECK
 DETECTOR ASSEMBLY TO BE SECURED WITH CHAIN AND LOCK IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 5) FIRE PUMP INSTALLATION TO COMPLY WITH THE
 REQUIREMENTS OF NFPA 20, 2003.