| Plan Review Notes For Permit 08120329 |
| Permit Number |
08120329 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-23 15:32:10 | PLANS APPROVED AND STAMPED ON THIS DATE. | | | | | | 1) TWO (2) HOUR HYDROSTATIC TEST REQUIRED PER NFPA 13, | | | 2002. | | | | | | 2) FIRE SPRINKLER PIPE INSPECTION REQUIRED. CODE 603 | | | | | | 3) FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED WITH | | | KNOX LOCKING CAPS PRIOR TO FINAL INSPECTION. | | | | | | 4) IN ADDITION TO ELECTRONIC SUPERVISION, DOUBLE CHECK | | | DETECTOR ASSEMBLY TO BE SECURED WITH CHAIN AND LOCK IN | | | ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 5) FIRE PUMP INSTALLATION TO COMPLY WITH THE | | | REQUIREMENTS OF NFPA 20, 2003. |
|