Plan Review Notes
Plan Review Notes For Permit 08120314
Permit Number 08120314
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-19 14:44:22 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 3} A LAUNDRY RECEPTACLE OUTLET(S) IS SUPPLIED BY A
 20-AMPERE BRANCH CIRCUIT. THIS CIRCUIT CAN HAVE NO
 OTHER OUTLETS. SEE 210.11(C)(2) FOR FURTHER
 INFORMATION.*** THE PANEL SCHEDULE INDICATES THE
 EXTERIOR
  
 4} THE DRYER RATED AT 5000 WATTS ON THE PANEL SCHEDULE
 IS SHOWN WITH A 20 MP OVER CURRENT PROTECTION, AND
 SHOWN AS EXISTING. THE DRYER CALCULATION SHOULD BE
 5000/240=20.83 A25 AMP BREAKER (240.6) AND #10
 CONDUCTORS (310.16). ALSO THE FRAME IS REQUIRED TO BE
 GROUNDED WITH AN EQUIPMENT GROUNDING CONDUCTOR PER
 250.140 AND 251.122.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  