| Date |
Text |
| 2009-01-12 13:22:22 | 2004 FBC W/2007 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 3) SUBMIT TWO (2) COPIES OF ENERGY CALCULATION FORMS AS |
| | REQUIRED BY FBC 13-600. |
| | |
| | 4) THE MINIMUM R-VALUE FOR A 2 X 6 FRAME WALL IS R-19 |
| | PER FBC 13-602.1.C.1.1. PLEASE REVISE WALL SECTION ON |
| | A-2. |
| | |
| | 5) THE R-30 BATT CEILING INSULATION SPECIFIED ON A-2 IS |
| | 9-1/2" THICK AND WILL NOT ALLOW FOR FREE AIR FLOW |
| | BETWEEN THE 2 X 8 RAFTERS/JOISTS. THE MINIMUM ALLOWED |
| | FOR A SINGLE ASSEMBLY ROOF IS R-19 WHICH IS 5-1/2" |
| | THICK. SEE FBC 13-604.1.ABC.1. PLEASE REVISE. |
| | |
| | 6) SHOW COMPLIANCE WITH R703.6.3. WHERE CEMENT PLASTER |
| | (STUCCO) IS TO BE APPLIED TO LATH OVER FRAME |
| | CONSTRUCTION, MEASURES SHALL BE TAKEN TO PREVENT |
| | BONDING BETWEEN THE CEMENT PLASTER AND THE |
| | WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED |
| | BETWEEN THE WATER-RESISTIVE BARRIER AND THE CEMENT |
| | PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING: |
| | 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER |
| | MATERIAL; OR |
| | 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER |
| | OVER AN APPROVED PLASTIC HOUSE WRAP; OR |
| | 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN |
| | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 7) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 8) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE ROOF |
| | COVERING IS FOR UNDERLAYMENT AND IS NOT FOR A FLAT ROOF |
| | SYSTEM. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | FLAT ROOF SYSTEM THAT WILL BE INSTALLED. SPECIFY WHICH |
| | ONE OF THE APPROVED ASSEMBLIES LISTED IN THE NOA WILL |
| | BE USED. SPECIFY THE FASTENING OPTION AND DESIGN |
| | PRESSURE THAT WILL BE USED. PROVIDE RAS 117 FOR |
| | ENHANCED FASTENING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY LIMITATION #7 OF THE NOA. DCA RULE 9B-72 |
| | |
| | 9) THE VALUE FOR THE ADDITION SPECIFIED ON THE |
| | APPLICATION IS LOW. BASED ON THE ICC BUILDING VALUATION |
| | DATA THE COST FOR 312 SQFT TYPE VI CONSTRUCTION IS |
| | $30,210.00. THE VALUE HAS BEEN ADJUSTED AND ADDITIONAL |
| | FEES OF $599.67 ARE DUE. FBC 108.3* CITY AMENDMENTS |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |