| Plan Review Notes For Permit 08120295 |
| Permit Number |
08120295 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-07 15:07:42 | ***DENIED*** | | | | | | 1) HOOD/SUPPRESSION TO MEET ALL REQUIREMENTS OF UL 300 | | | (WET CHEMICAL SYSTEMS) AND NFPA 96. | | | | | | 2) AN AUDIBLE/VISUAL DEVICE IS REQUIRED TO NOTIFY | | | OCCUPANTS IN THE EVENT OF SUPPRESSION ACTIVATION. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR HOOD | | | AND SUPPRESSION SYSTEMS. | | | | | | 4) PROVIDE DETRAILS ILLUSTRATING ASSOCIATED EQUIPMENT | | | AND LOCATION OF THE MANUAL MEANS OF ACTIVATION. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|