| 2008-12-26 15:59:50 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING SCHEDULE FOR |
| | LIGHTING BEING CONTROLLED BY LCP. |
| | PLEASE INDICATE THE REQUIRED MINIMUM 10HR BATTERY BACK |
| | UP FOR THE ASTRONOMICAL TIME CLOCK. |
| | PLEASE SEE SECTION FOR LIGHTING THAT IS REQUIRED TO BE |
| | CONTROLLED AT POINT OF ENTRANCE AND SO THAT THE |
| | OCCUPANT CAN VISUALLY SEE ALL LIGHTING BEING CONTROLLED |
| | OR MEET EXCEPTIONS. AS THIS HAS BEEN A COMMON NOTED ON |
| | OTHER PROJECTS PERHAPS A SMALL TYPICAL DETAIL FOR THE |
| | TYPICAL KEYPAD BEING USED WHICH SHOWS THE OVER RIDES AS |
| | BEING LIT, AND A TYPICAL LABELING OF THE SAME OVER |
| | RIDES. PLEASE CALL TO GO OVER THIS IF DESIRED. |
| | A TYPICAL KEYPAD IS USED ON MANY PROJECTS WHICH |
| | INDICATES THE LIGHTED OVER RIDES AND SIGNAGE. |
| | 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4. |
| | .1.4 FOR EXTERIOR. |
| | |
| | 2) NOTE: PLEASE COMPLETE THE FIXTURE INFORMATION, |
| | LEGEND AND PLANS. PLEASE SEE FIXTURES SUCH AS FIXTURE |
| | *C* WHICH IS SHOWN ON PLANS IS NOT ON ANY LEGEND. |
| | PLEASE SEE FBC 13-415.2.ABC.1.1, AND .1.2. ALL WATTAGES |
| | ARE BASED ON THE RATING OF THE FIXTURE NOT THE BULB |
| | WATTAGES USED. |
| | PLEASE SEE 13-415.2.ABC.1.2 (3.) AS THIS GIVES THE |
| | MINIMUM VA TO BE 30VA PER FT OF TRACK OR THE TOTAL |
| | NUMBER OF FIXTURES AT THE RATED VA PER FIXTURE WHICH |
| | EVER IS GREATER. |
| | |
| | 3) NOTE: PLEASE SEE 220.43A ALONG WITH COMMENTARY |
| | ATTACHED BELOW DIRECTLY FROM THE NEC. THE LOAD USED TO |
| | SIZE THE BRANCH CIRCUIT MAY BE THE 180VA ONLY WHEN |
| | SIZING THE BRANCH OR THE 200VA PER FT. HOWEVER PER |
| | 220.43A, THE LOAD REQUIRED TO SIZE FEEDERS IS 200VA PER |
| | FOOT NOT 180VA PER RECEPTACLE. I HAVE EXTRACTED THE |
| | SECTION FROM THE CODE. PLEASE READ THE LAST TWO |
| | SENTENCES AS THIS IS FROM THE HANDBOOK COMMENTARY WHICH |
| | CLEARLY NOTES THE LOAD TO BE FIGURED FOR FEEDERS. |
| | |
| | **** 220.43 SHOW-WINDOW AND TRACK LIGHTING |
| | (A) SHOW WINDOWS FOR SHOW-WINDOW LIGHTING, A LOAD OF |
| | NOT LESS THAN 660 VOLT-AMPERES/LINEAR METER OR 200 |
| | VOLT-AMPERES/LINEAR FOOT SHALL BE INCLUDED FOR A SHOW |
| | WINDOW, MEASURED HORIZONTALLY ALONG ITS BASE. |
| | FPN:SEE 220.14(G) FOR BRANCH CIRCUITS SUPPLYING SHOW |
| | WINDOWS. |
| | |
| | THE CALCULATION OF 200 VOLT-AMPERES FOR EACH LINEAR |
| | FOOT OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE |
| | FEEDER LOAD. SEE THE COMMENTARY FOLLOWING 220.14(G) FOR |
| | LOAD CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS. |
| | |
| | *** |
| | |
| | 4) NOTE: PLEASE SEE 600.5, 215.3, 230.42 ETC AS THE |
| | SIGN CIRCUIT IS A LIGHTING LOAD TO BE SHOWN AT 125%. |
| | |
| | 5) NOTE: NO LIGHTING FOR EGRESS PATH UP TO ELECTRIC |
| | EQUIPMENT PANELS IS SHOWN. PLEASE SEE 700.12F, 700.16, |
| | NFPA-101 7.8.1.3, 7.8.1.2.2, 7.9.1.2, 7.9.2.2, FBC |
| | 1006.1.2 ETC |
| | |
| | 6) NOTE: PLEASE FBC 108.3. ALL EQUIPMENT, DESIGN COST, |
| | MATERIALS AND LABOR SHALL BE INCLUDING EVEN IF ANY OF |
| | THESE ITEMS ARE OWNER SUPPLIED. |
| | THE APPLIED VALUE FOR SCOPE AS SHOWN IS LOW. THIS |
| | COMMENT IS NOT FOR THE DESIGNER. |
| | |
| | 7) NOTE: PLEASE COORDINATE PANELS AND RISER. SEE PANEL |
| | *A* SHOWN AS MLO AND ON RISER AS MCB. |
| | 225,230, 215, 240, ETC |
| | FBC 106.1.1, 106.1.2 FOR COORDINATION AND CLARITY. |
| | |
| | 8) NOTE: PLEASE SEE NEC 210.8B2 FOR ALL 15AMP AND 20AMP |
| | RECEPTACLES CIRCUITS INSIDE KITCHEN AREAS WHICH ARE |
| | REQUIRED TO BE GFI OR GFI PROTECTED. THIS IS REQUIRED |
| | WHETHER OR NOT THEY ARE RECEPTACLES ONLY FEEDING |
| | COUNTER SPACES. |
| | |
| | 9) NOTE: PLEASE SEE NOTE AT THE BOTTOM OF SHEET 2.1E |
| | WHICH REFERENCES TO SEE SHEET 3.2P FOR ELECTRICAL ON |
| | ROOF-TOP, HOWEVER THERE IS NO SHEET 3.2P IN PLANS |
| | SUBMITTED. |
| | THERE IS HOWEVER A SHEET 3.2M WHICH INDICATES THE ROOF |
| | TOP ELECTRICAL. THIS SEEMS TO HAVE BEEN A MISPRINT AND |
| | COULD HAVE BEEN REDLINED. HOWEVER SHOULD BE REVISED AT |
| | THIS TIME WITH OTHER COMMENTS. |
| | |
| | 10) NOTE: PLEASE REVISE CODE REFERENCE ON ELECTRICAL |
| | PLANS. THE COVER SHEET IS CORRECT HOWEVER SEE 2.0E. |
| | FBC 2004 W/2007 REVISIONS. |
| | ALSO ANOTHER ITEM WHICH COULD HAVE BEEN REDLINED |
| | HOWEVER PLANS WERE COMING BACK FOR CORRECTIONS. |
| | |
| | 11) NOTE: WHERE IS THE LIGHTING CONTROL PANEL GOING TO |
| | BE LOCATED? NOT SHOWN ON LIGHTING OR POWER PLANS. |
| | 110.26, 240.24 ETC |
| | FBC 106.1.1, .1.2 FOR ADDITIONAL INFORMATION, |
| | COORDINATION, AND CLARITY OF RECORD PLANS. |
| | |
| | 12) NOTE: PLEASE SEE 422.13 AS THE ELECTRIC STORAGE |
| | TYPE WATER HEATER LOAD IS REQUIRED TO BE SHOWN AT 125%. |
| | PLEASE SEE THE 2005 NEC HANDBOOK WHICH PROVIDES A |
| | COMMENTARY OF THE REVISION IN THE 2005 NEC. |
| | PLEASE SEE THE LAST SENTENCE OF COMMENTARY. |
| | |
| | 13) NOTE: PLEASE SEE POWER PLANS. THE WATER HEATER IS |
| | BEING SHOWN IN THE BATHROOM ON A RECEPTACLE WHICH IS |
| | NOT PERMITTED. ANOTHER WATER HEATER IS SHOWN ON THE |
| | SECOND FLOOR EQUIPMENT ROOM AREA LAYOUT HOWEVER THIS |
| | SEEMS TO BE THE SAME WATER HEATER. EACH UNIT SHOWN |
| | CONTAINS THE SAME CIRCUIT B-37, 39. |
| | PLEASE SEE 422.30,31 A DISCONNECTING MEANS OF SOME TYPE |
| | IS REQUIRED. THE WATER HEATER ON THE SECOND FLOOR DOES |
| | ACTUALLY SHOW THE REQUIRED DISCONNECT. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |