| Plan Review Notes For Permit 08120285 |
| Permit Number |
08120285 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2009-08-05 17:39:31 | | | | ** DENIED REVIEW OF REVISIONS ** | | | | | | 1) NOTE: PLANS HAVE BEEN REVISED TO NOW INCLUDE MANUAL | | | TRANSFER SWITCH FOR TENANT SPACE. HOW WILL FEED COME | | | INTO BUILDING FOR TRANSFER SWITCH? | | | PLEASE SHOW HOW THIS WILL TAKE PLACE. | | | PLEASE EXPLAIN HOWEVER AND WHERE THE DISCONNECT MEANS | | | WILL BE PROVIDED FOR POWER FROM GENERATOR. | | | PLEASE SEE 225.34, 225.31-225.39, ALSO 702.11. | | | | | | 2) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE NEW PROPOSED MTS. 90.7,110.3, 702.6. | | | | | | 3) NOTE: PANEL SCHEDULES AND LOAD CALCULATIONS HAVE | | | REVISED ITEMS SHOWN IN REV #4 HOWEVER NO OTHER | | | ELECTRICAL PLANS FOR LAYOUT OF ELECTRICAL EQUIPMENT WAS | | | SUBMITTED TO REVISE THE ACTUAL ITEMS ON PLANS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|