| Date |
Text |
| 2009-02-27 17:48:35 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | CITY WPB MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | |
| | 6. SHT P1 SHOWS THE DISH WASHER DRAINING THROUGH THE |
| | GREASE TRAP. PER ARTICLE III SECTION 90-124(7)(B) |
| | GREASE TRAPS ARE TO BE INSTALLED OUTSIDE THE FLLD |
| | PREPARATION AREA WITH THE DISH WASHER DISCHARGING VIA A |
| | SEPARATE LINE. |
| | ****RESPONSE NOTED, BUT THE DISHWASHER IS STILL |
| | DISCHARGING THRU THE GREAS TRAP. THE DISH WASHER SHALL |
| | DISCHARGE DOWNSTREAM OF THE GREASE TRAP. |
| | |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | |
| | 11. SHT P2 WATER HEATER PIPING DETAIL SHOWS THE P&T |
| | DISCHARGE LINE TO THE EXTERIOR AND ALSO TO THE |
| | EMERGENCY WATER HEATER PAN. THE DETAIL ALSO SHOWS AN |
| | EXPANSION TANK AND A WATTS MODEL 530 VALVE FOR |
| | EXPANSION RELIEF. PLEASE CLARIFY. SECTIONS 106.1.1, |
| | 504.6.1 & 607.3.1/607.3.2. |
| | ****RESPONSE NOTED, BUT THE P/T AND PAN DRAIN ARE NOW |
| | INDICATING AS BEING RUN TO THE MECHANICAL ROOM. PLEASE |
| | CLARIFY. PLEASE INDICATE THE "SAFE PLACE OF DISPOSAL" |
| | FOR THE P/T VALVE AS REQUIRED IN SECTION 504.6.1. ALSO |
| | THE PAN DRAIN SHALL TERMINATE OVER A SUITABLY LOCATED |
| | INDIRECT WAST RECEPTOR OR FLOOR DRAIN OR EXTEND TO THE |
| | EXTERIOR OF THE BUILDING. SECTION 504.7.2. PLEASE |
| | INDICATE THE TERMINATION POINT FOR THE PAN DRAIN. -- |
| | DETAIL NOW SHOWS THE DRAIN LINE FROM THE WATTS MODEL |
| | 530C THERMAL EXPANSION VALVE DRAINING INTO THE PAN. THE |
| | WATER HEATER SHALL BE RAISED IN THE PAN TO KEEP IT FROM |
| | SITTING IN WATER DISCHARGE FROM THE VALVE. SECTION |
| | 303.2. |
| | |
| | 12. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |