| 2009-03-05 09:45:28 | NOTE ADDED 3/5/08 |
| | |
| | THE LIFE SAFETY CODE NOTED ON PLANS STATES THE 2005 |
| | EDITION. HOWEVER THERE IS A 2003 OR 2006. THERE IS NO |
| | 2005. THIS PROJECT AS APPLIED FOR PERMIT IS UNDER THE |
| | 2003 NFPA-101. PLEASE ADJUST NOTES WHEN MAKING CHANGES |
| | TO PLANS. |
| 2009-03-04 14:38:19 | ** DENIED 2ND REVIEW ** |
| | |
| | ** SOME ITEMS REQUESTED TO SHOW MINIMUM CODE COMPLIANCE |
| | IS NOW ON PLANS FOR FIRST REVIEW. |
| | |
| | 1) NOTE: A COMMENT PREVIOUSLY MADE BY THE FIRE MARSHAL |
| | REVIEWER WITH RESPECT TO CO2 DETECTORS WAS ANSWERED |
| | WITH A STATEMENT THAT THE OVEN HAS NOW BEEN REMOVED. |
| | HOWEVER THE FACT IS PER THE ELECTRICAL PLANS THE OVEN |
| | AS WELL AS THE COOK-TOP STILL EXISTS. |
| | ** THIS IS NOTED FOR INFORMATION AND WILL BE FORWARDED |
| | TO THE FIRE REVIEWER. THIS MAY ELECTRICAL PLANS |
| | DEPENDING ON COMMENTS AND TYPE OF EQUIPMENT BEING |
| | INSTALLED.. |
| | |
| | 2) NOTE: ON PREVIOUS REVIEW THE CODE SECTION WAS GIVEN |
| | WITH RESPECT TO THE STORAGE TYPE WATER HEATERS NEEDING |
| | TO HAVE LOAD FIGURED AS A CONTINUOUS LOAD. THE RESPONSE |
| | MENTIONS REVISED LOADS ARE NOW SHOWN. HOWEVER THE WATER |
| | HEATER STATES IT IS SHOWN AT 125% WHICH IS 3KW. IF THE |
| | UNIT IS 3KW, THEN THE 125% REQUIRED WOULD BE ABOVE |
| | THIS. THE UNIT ON THE PLANS AS WELL AS THE PLUMBING |
| | PLANS INDICATES THE BASE KW AT 3KW. |
| | PLEASE ADJUST. 422.13, 220. |
| | |
| | 3) NOTE: PREVIOUS REVIEW REQUESTED TO SUBMIT AND SHOW |
| | LIGHTING PERFORMANCE CALCULATIONS/LIGHTING DENSITIES |
| | PER 13-415.2,13-415.2.ABC.1.1 AND .1.2. |
| | THE PLANS HAVE NOW BEEN REVISED TO INCLUDE CALCULATIONS |
| | HOWEVER CODE COMPLIANCE DOES NOT APPEAR TO BE CORRECT. |
| | FOR EXAMPLE: |
| | ROOM #305 DOES NOT INCLUDE ANY OF THE *K* FIXTURES ON |
| | THE CALCULATIONS. THE BD FIXTURES ARE ALSO SHOWN AT A |
| | MUCH LOWER WATTAGE ON THE TABLE ALONG WITH A NUMBER OF |
| | FIXTURES LOWER THEN WHAT IS SHOWN ON PLANS. |
| | ANOTHER ROOM WOULD BE #307. |
| | |
| | FOR EXAMPLE: THE NOTES AT THE BOTTOM OF THE |
| | CALCULATIONS ALSO STATES THERE ARE LIGHTS EXEMPT PER |
| | 13-415.2.ABC.1.1. PLEASE SEE THIS SECTION OF THE CODE |
| | WHICH ONLY EXEMPTS LIGHT IN ANY ONE ARE FROM BEING |
| | FIGURED IN THE CALCULATIONS IF THE OTHER LIGHTING IN |
| | THE AREA WHICH IS CONTROLLED COMPLETELY SEPARATELY IS |
| | THE GREATER OF THE TWO. IN ORDER TO USE THIS EXEMPTION, |
| | THERE MUST BE ALIGHTING SYSTEM OR CONTROLS IN PLACE |
| | WHICH DOES NOT PERMIT BOTH POSSIBLE AREAS/ZONES ETC |
| | FROM BEING *ON* AT THE SAME TIME. BASED ON THE LIGHTING |
| | CONTROLS SHOWN IT IS POSSIBLE FOR ALL LIGHTS TO BE ON |
| | AT THE SAME TIME. |
| | IF SUCH SYSTEM EXISTS PLEASE PROVIDE WIRING DETAILS OR |
| | SYSTEM ON PLANS. |
| | |
| | FOR EXAMPLE: THE ARCHITECTURAL PLANS SHOW THE LIGHTING |
| | FIXTURES AND LAYOUTS WHICH ARE NOT THE SAME ON THE |
| | ELECTRICAL PLANS. ONE LOCATION WOULD BE ROOM 310. |
| | |
| | *** PLEASE BE SIRE TO GO OVER THE REST OF THE |
| | CALCULATIONS AS THERE ARE OTHER AREAS IN WHICH THE |
| | LIGHTING CALCULATIONS DO NOT INDICATE THE WATTAGES |
| | SHOWN ON THE FIXTURE LEGEND. PLEASE KEEP IN MIND THE |
| | WATTAGES ARE BASED ON THE RATINGS OF THE FIXTURES NOT |
| | THE BULBS INCLUDING THE POWER FACTORS OF BALLAST ON |
| | HID/FLUORESCENT FIXTURES. |
| | |
| | ** THE ABOVE ARE ONLY A FEW EXAMPLES GIVEN AS A BENEFIT |
| | TO THE DESIGN TEAM. THESE EXAMPLES MAY NOT BE AN |
| | EXHAUSTED LIST. |
| | |
| | 4) NOTE: PLEASE IDENTIFY THE ROOF TOP GFI FOR THE |
| | CONDENSING UNITS. PER 210.63,210.8B3 NEW COMMENT |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |