| 2009-01-09 12:04:11 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. THE WOLF VENTLESS HOOD INSTALLED ABOVE THE COOKTOP |
| | SHALL BE TESTED IN ACCORDANCE WITH UL 197 FOR |
| | COMMERCIAL KITCHEN RECIRCULATING SYSTEMS PER FBCM |
| | 507.1(2). PROVIDE SUPPORTING DOCUMENTATION. |
| | |
| | 2. OTHER HEAT PRODUCING APPLIANCES IN THE KITCHEN (SUCH |
| | AS THE OVEN) SHALL BE PROVIDED WITH A TYPE II HOOD IN |
| | ACCORDANCE WITH FBCM 507.2.2. |
| | |
| | 3. AHU HANGING DETAIL CALLS FOR AN AUXILIARY PAN DRAIN |
| | FROM AN AUXILIARY DRAIN PAN. THE AUXILIARY PAN DRAIN |
| | SHALL DISCHARGE TO A CONSPICUOUS POINT OF DISPOSAL TO |
| | ALERT OCCUPANTS IN THE EVENT OF A STOPPAGE OF THE |
| | PRIMARY DRAIN IN ACCORDANCE WITH FBCM 307.2.3(1). |
| | PLEASE SHOW THE LOCATION OF THE AUXILIARY DRAIN |
| | DISCHARGE TO DEMONSTRATE COMPLIANCE WITH THIS SECTION. |
| | NOTE: ANY OF THE METHODS OF AUXILIARY/SECONDARY DRAIN |
| | PROTECTION LISTED UNDER FBCM 307.2.3 MAY BE EMPLOYED |
| | AND SHOWN ON PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 4. ALUMINUM ROOF STAND APPEARS TO BE OF THE |
| | PRE-ENGINEERED TYPE. PRE-ENGINEERED A/C STANDS ARE |
| | DEFINED AS STRUCTURAL COMPONENTS IN ACCORDANCE WITH FAC |
| | RULE 9B-72. PLEASE PROVIDE PRODUCT APPROVAL FOR THE |
| | STAND TO BE USED, REVIEWED AND APPROVED BY THE DESIGNER |
| | OF RECORD IN ACCORDANCE WITH FBCB 106.3.3. |
| | |
| | 5. PLANS CALL FOR AN 18? ELEVATION FROM THE FOOT OF THE |
| | A/C STAND TO THE BOTTOM OF THE BEAM. THE ELEVATION OF |
| | THE STAND SHALL BE DETERMINED IN ACCORDANCE WITH FBCB |
| | TABLE 1509.7 BASED ON THE WIDTH OF THE ELEVATED |
| | APPLIANCE. THIS MEASUREMENT SHALL BE FROM ABOVE THE |
| | ROOF SURFACE. PROVIDE DIMENSIONS OF THE CONDENSERS TO |
| | CONFIRM REQUIRED HEIGHT OF STANDS AND THE SIZE OF |
| | CONDENSER ALLOWED ON THE STAND PER THE PRODUCT APPROVAL |
| | DOCUMENTATION. |
| | |
| | 6. MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT |
| | ARE EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES IN ACCORDANCE WITH FBCM |
| | 301.13. PROVIDE INFORMATION SHOWING OUTDOOR APPLIANCES, |
| | SUCH AS CONDENSING UNITS, ARE DESIGNED TO RESIST WIND |
| | PRESSURES IN ACCORDANCE WITH THIS SECTION. |
| | |
| | 7. DETAIL CALLS FOR RUSKIN FIRE/SMOKE DAMPER TO BE |
| | INSTALLED AT RATED WALL ASSEMBLIES. PLEASE SHOW HOW |
| | SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH |
| | FBCM 607.3.2.1. |
| | ALSO, ELECTRICAL PLANS SHOW NO PROVISIONS FOR POWER TO |
| | THE SMOKE DAMPER ACTUATING MOTORS. PLEASE COORDINATE |
| | MECHANICAL AND ELECTRICAL PLANS IN ACCORDANCE WITH FBCB |
| | 106.1.1. |
| | |