Plan Review Notes
Plan Review Notes For Permit 08120284
Permit Number 08120284
Review Stop P
Sequence Number 3
Notes
Date Text
2009-06-15 16:19:03DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 RESIDENTIAL
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
  
 2. SHT A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FIXTURE LAYOUT ON THE FLOOR PLAN, NOR DOES
 IT MEET CODE. MOST PIPE SIZES ARE NOT SHOWN. SHOW ALL
 PIPE SIZES TO VERIFY COMPLIANCE WITH TABLES 709.1,
 710.1(1), 710.1(2) & 916.1.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM STILL DOES
 NOT REFLECT THE FLOOR PLAN. THE BUILDING DRAIN ENTERS
 FROM THE SOUTH AND TURNS EAST TO PICK UP THE WASH
 MACHINE, TURNS EAST TO PICK UP THE KITCHEN SINK AND
 THEN TURNS EAST TO PICK UP EACH BATHROOM GROUP. THE
 RISER SHOWS THE BATHROOM GROUPS EITHER GOING TO THE
 WEST OR STRAIGHT TO THE SOUTH. PLEASE CORRELATE. ALSO
 AS SHOWN THE TUBS ARE NOT VENTED. SECTION 901.2.1.
 ******NO RESPONSE, COMMENT NOT ADDRESSED. (SAME SHEET
 RESUBMITTED).
  
 2A. OK
 2B. OK
  
 2C. SUBMIT A SANITARY RISER DIAGRAM THAT REFLECTS THE
 RED-LINE PIPING INDICATED ON SHT A3 OF ONE SET OF PLAN
 SHOWING ALL PIPE SIZES, TRAPS & VENTS AS REQUIRED IN
 CHAPTERS 7, 9 & 10.
 ****RESPONSE NOTED, BUT THE RED-LINE DRAWING WAS
 DISREGARDED. SEE NEW RED-LINE EXAMPLE OF CODE COMPLIANT
 RISER SECTION THAT REFLECTS THE FLOOR PLAN.
 ******NO RESPONSE, COMMENT NOT ADDRESSED. (SAME SHEET
 RESUBMITTED).
  
  
 ********NEW COMMENT********
  
 1B. MINIMUM 2 SETS OF PLANS SHALL BE SUBMITTED WITH
 EACH APPLICATION FOR PERMIT. SECTION 106.1. ONLY ONE
 SET OF PLANS WAS SUBMITTED FOR REVIEW. SOME SAME SHEETS
 FROM PREVIOUS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved