| Date |
Text |
| 2009-06-15 16:19:03 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 RESIDENTIAL |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. OK |
| | |
| | 2. SHT A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FIXTURE LAYOUT ON THE FLOOR PLAN, NOR DOES |
| | IT MEET CODE. MOST PIPE SIZES ARE NOT SHOWN. SHOW ALL |
| | PIPE SIZES TO VERIFY COMPLIANCE WITH TABLES 709.1, |
| | 710.1(1), 710.1(2) & 916.1. |
| | ****RESPONSE NOTED, BUT THE RISER DIAGRAM STILL DOES |
| | NOT REFLECT THE FLOOR PLAN. THE BUILDING DRAIN ENTERS |
| | FROM THE SOUTH AND TURNS EAST TO PICK UP THE WASH |
| | MACHINE, TURNS EAST TO PICK UP THE KITCHEN SINK AND |
| | THEN TURNS EAST TO PICK UP EACH BATHROOM GROUP. THE |
| | RISER SHOWS THE BATHROOM GROUPS EITHER GOING TO THE |
| | WEST OR STRAIGHT TO THE SOUTH. PLEASE CORRELATE. ALSO |
| | AS SHOWN THE TUBS ARE NOT VENTED. SECTION 901.2.1. |
| | ******NO RESPONSE, COMMENT NOT ADDRESSED. (SAME SHEET |
| | RESUBMITTED). |
| | |
| | 2A. OK |
| | 2B. OK |
| | |
| | 2C. SUBMIT A SANITARY RISER DIAGRAM THAT REFLECTS THE |
| | RED-LINE PIPING INDICATED ON SHT A3 OF ONE SET OF PLAN |
| | SHOWING ALL PIPE SIZES, TRAPS & VENTS AS REQUIRED IN |
| | CHAPTERS 7, 9 & 10. |
| | ****RESPONSE NOTED, BUT THE RED-LINE DRAWING WAS |
| | DISREGARDED. SEE NEW RED-LINE EXAMPLE OF CODE COMPLIANT |
| | RISER SECTION THAT REFLECTS THE FLOOR PLAN. |
| | ******NO RESPONSE, COMMENT NOT ADDRESSED. (SAME SHEET |
| | RESUBMITTED). |
| | |
| | |
| | ********NEW COMMENT******** |
| | |
| | 1B. MINIMUM 2 SETS OF PLANS SHALL BE SUBMITTED WITH |
| | EACH APPLICATION FOR PERMIT. SECTION 106.1. ONLY ONE |
| | SET OF PLANS WAS SUBMITTED FOR REVIEW. SOME SAME SHEETS |
| | FROM PREVIOUS REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |