Plan Review Notes
Plan Review Notes For Permit 08120284
Permit Number 08120284
Review Stop E
Sequence Number 2
Notes
Date Text
2009-02-26 14:37:44 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW AND WERE
 NOT RESPONDED TO.SHEET A2..
  
 9} CIRCUIT #12 IS FOR A DISPOSAL, NOT IN THE LOAD
 CALCULATION.220.83(B)(3).
  
 THESE COMMENTS ARE GENERATED BY CHANGES MADE TO THE
 PLANS:
  
 1} THE PLAN INDICATES A MAIN DISCONNECT (TWO ACTUALLY)
 AT THE METER, THERE IS NO DISCONNECT ON THE RISER
 DIAGRAM RISER DIAGRAM, CORRELATE AND INDICATE THE
 INTENT OF THE DESIGNER.DUE TO THE METER LOCATION, A
 DISCONNECT IS REQUIRED PER 230.70
  
 2}THE PANEL SHOWN ON THE RISER IS RATED AT 200 AMPS
 WITH A225 AMP MAIN IN VIOLATION OF 408.36(A) LIGHTING
 AND APPLIANCE BRANCH-CIRCUIT PANELBOARD INDIVIDUALLY
 PROTECTED EACH LIGHTING AND APPLIANCE BRANCH-CIRCUIT
 PANELBOARD SHALL BE INDIVIDUALLY PROTECTED ON THE
 SUPPLY SIDE BY NOT MORE THAN TWO MAIN CIRCUIT BREAKERS
 OR TWO SETS OF FUSES HAVING A COMBINED RATING NOT
 GREATER THAN THAT OF THE PANELBOARD. ALSO THE
 CONDUCTORS ARE RATED FOR 200 AMPS, 3/0 WOULD BE
 REQUIRED FOR 225 AMPS.
  
 3} THE PANEL SCHEDULE CIRCUITS 2&4 FOR THE AHU SHOWS A
 60 AMP BREAKER FOR A 47 AMP LOAD IN VIOLATION OF 240.4.
 THE HEAT LOAD IS STATED TO BE 7500 WATTS IN THE LOAD
 CALCULATIONS. 7500/240X125%=39 AMPS THEREFORE A 40 AMP
 BREAKER WOULD BE USED. 240.4(B).
  
 THE FOLLOWING COMMENTS ARE IN REGARD TO THE PANEL
 SCHEDULE:
  
 4} CIRCUITS #1 & 3 HAVE NO OVERCURRENT RATING FOR THE
 OCP.A/C CIRCUIT.
  
 5} THERE IS A GARAGE GFI CIRCUIT #15 LISTED, BUT NO
 GARAGE SHOWN ON THE PLAN. 408.4
  
 6} CIRCUIT #18 LISTS THE "UTIL" ON WITH THE BATH
 CIRCUIT IN VIOLATION OF 210.11(C)(3) " BATHROOM BRANCH
 CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS."
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD
 SHEETS TO EXPEDITE AND SUBMIT WRITTEN RESPONSE TO THE
 COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  