Plan Review Notes For Permit 08120284
Permit Number 08120284
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-24 13:46:59DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 RESIDENTIAL
  
 1. SHT A1 BUILDING CODE/DESIGN CRITERIA SHALL ALSO
 INCLUDE THE 2007 AMENDMENTS TO THE FBC-2004.
  
 2. SHT A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FIXTURE LAYOUT ON THE FLOOR PLAN, NOR DOES
 IT MEET CODE. MOST PIPE SIZES ARE NOT SHOWN. SHOW ALL
 PIPE SIZES TO VERIFY COMPLIANCE WITH TABLES 709.1,
 710.1(1), 710.1(2) & 916.1.
  
 2A. THE WASH MACHINE, KITCHEN SINK & BOTH LAVS ARE NOT
 VENTED AS SHOWN. SECTION 901.2.
  
 2B. THE WASH MACHINE REQUIRES A STANDPIPE PER SECTIONS
 1002.1 THAT COMPLIES WITH SECTION 802.4. (MINIMUM 18" &
 MAXIMUM 42") & ALSO REQUIRES A CLEANOUT MINIMUM 4 FEET
 ABOVE THE FLOOR PER SECTION 708.9.
  
 2C. SUBMIT A SANITARY RISER DIAGRAM THAT REFLECTS THE
 RED-LINE PIPING INDICATED ON SHT A3 OF ONE SET OF PLAN
 SHOWING ALL PIPE SIZES, TRAPS & VENTS AS REQUIRED IN
 CHAPTERS 7, 9 & 10.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  