| 2008-12-24 13:46:59 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 RESIDENTIAL |
| | |
| | 1. SHT A1 BUILDING CODE/DESIGN CRITERIA SHALL ALSO |
| | INCLUDE THE 2007 AMENDMENTS TO THE FBC-2004. |
| | |
| | 2. SHT A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FIXTURE LAYOUT ON THE FLOOR PLAN, NOR DOES |
| | IT MEET CODE. MOST PIPE SIZES ARE NOT SHOWN. SHOW ALL |
| | PIPE SIZES TO VERIFY COMPLIANCE WITH TABLES 709.1, |
| | 710.1(1), 710.1(2) & 916.1. |
| | |
| | 2A. THE WASH MACHINE, KITCHEN SINK & BOTH LAVS ARE NOT |
| | VENTED AS SHOWN. SECTION 901.2. |
| | |
| | 2B. THE WASH MACHINE REQUIRES A STANDPIPE PER SECTIONS |
| | 1002.1 THAT COMPLIES WITH SECTION 802.4. (MINIMUM 18" & |
| | MAXIMUM 42") & ALSO REQUIRES A CLEANOUT MINIMUM 4 FEET |
| | ABOVE THE FLOOR PER SECTION 708.9. |
| | |
| | 2C. SUBMIT A SANITARY RISER DIAGRAM THAT REFLECTS THE |
| | RED-LINE PIPING INDICATED ON SHT A3 OF ONE SET OF PLAN |
| | SHOWING ALL PIPE SIZES, TRAPS & VENTS AS REQUIRED IN |
| | CHAPTERS 7, 9 & 10. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |