| Plan Review Notes For Permit 08120284 |
| Permit Number |
08120284 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-22 19:07:49 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. ENERGY CALCULATIONS SHALL BE SIGNED BY THE | | | PREPARER/OWNER IN ACCORDANCE WITH FBCB 13-103.1.2. | | | | | | 2. PLANS DO NOT SHOW THE SIZE OF RETURN AIR TRANSFER | | | DUCTS. SHOW SIZE OF TRANSFER DUCTS AND 1" UNDERCUT ON | | | BEDROOM DOORS TO DEMONSTRATE COMPLIANCE WITH THE | | | EXCEPTION UNDER FBCR M1602.4. | | | | | | 3. PLEASE SHOW SIZE AND LOCATION OF DRYER AND BATHRROM | | | EXHAUST DUCTS, INCLUDING TERMINATION LOCATIONS FBCR | | | M1501.1 AND FBCR M1506.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|