| 2009-01-09 16:56:30 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |
| | 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY TO VERIFY IF IMPACT FEES ARE DUE AND HOW MUCH |
| | CREDIT IS GIVEN FOR THE EXISTING HOUSE. BRING BACK |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 3- NEED TO OBTAIN A SEPARATE PERMIT FOR THE DEMOLITION |
| | OF THE EXISTING HOUSE. |
| | |
| | 4- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW. VALUATION WAS UPDATED AS REQUIRED BY SEC. |
| | 108.3 OF CITY AMENDMENTS TO FBC 2004 TO $128,668. |
| | THEREFORE, OWES $2161.79 FOR UPDATED VALUATION AND |
| | RADON FEES. |
| | |
| | 5- PLANS TO SPECIFY ALL LIVE AND DEAD LOADS AS REQUIRED |
| | BY SEC. R301.1 AND TABLE R301.5 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. NOTE: ATTIC LIVE LOADS NEED TO BE |
| | INCLUDED ALSO. |
| | |
| | 6- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) PRECAST LINTELS AS SHOWN ON PLANS. |
| | |
| | B) ENTRY DOOR AND KITCHEN AND BEDROOM EXTERIOR DOORS. |
| | CLEARLY IDENTIFY WHICH PRODUCT APPROVAL IS FOR THE |
| | ENTRY AND ALL OTHER OPENINGS. |
| | ***NOTE: NOA 02-1211.10 SUBMITTED EXPIRED ON JULY 17, |
| | 2008. NEED TO PROVIDE CURRENT PRODUCT APPROVAL. |
| | |
| | C) HURRICANE SHUTTERS: PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. COMPLETE ALL THE |
| | INFORMATION AND CLEARLY MARK ON SHUTTERS DRAWINGS |
| | SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNTED, BUILD |
| | OUT, ETC) AND SPECIFIC ANCHOR TYPE AND SPACING TO BE |
| | USED. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- ENERGY CALCULATIONS: OWNER/AGENT TO SIGN AND DATE |
| | BOTTOM OF FORM. |
| | |
| | 9- SINCE THE ENERGY CALCULATIONS ARE TAKEN THE CEILING |
| | FAN CREDIT, THEN THE ELECTRICAL PLAN NEEDS TO SHOW SIZE |
| | OF CEILING FANS AS REQUIRED BY TABLE 13-607.1.A.1 OF |
| | FBC 2004. AND, THEY NEED TO BE INSTALLED FOR |
| | INSPECTION. |
| | |
| | 10- PROVIDE DRAINAGE PLAN TO SHOW COMPLIANCE WITH SEC. |
| | R401.3 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 11- SHEET A1: |
| | A) BEDROOM EGRESS WINDOWS SH-24 DON'T COMPLY WITH MIN. |
| | OPENING HEIGHT OF SEC. R310.1.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. REVISE WINDOW SIZE AND WINDOW OPENING |
| | DIMENSIONS SHOWN ON WINDOW SCHEDULE. |
| | |
| | B) SPECIFY ATTIC SIZE TO SHOW COMPLIANCE WITH SEC. R807 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) WINDOW BY TUB AREA ON BOTH BATHROOMS TO HAVE SAFETY |
| | GLASS AS REQUIRED BY SEC. R308.4 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | D) DESIGN PRESSURES SPECIFIED FOR DOOR AND WINDOWS |
| | DON'T CORRESPOND TO EXPOSURE "C" AS SHOWN ON BUILDING |
| | INFORMATION CHART. REVISE AS REQUIRED. |
| | ALSO, DESIGN PRESSURES SHOWN ON WINDOW/ DOOR SCHEDULES |
| | AND EXTERIOR ELEVATIONS ON SHEETS A2 AND A3 DON'T MATCH |
| | DESIGN PRESSURES SHOWN ON BUILDING INFORMATION CHART. |
| | REVISE AS REQUIRED. |
| | |
| | E) CLARIFY DOOR HEIGHT OF DOORS SHOWN ON THE DOOR |
| | SCHEDULE. ENTRY DOOR TO BE MIN. 3'-0" WIDE BY 6'-8" |
| | HEIGHT AS REQUIRED BY SEC. R311.4.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | F) MASTER BATHROOM TYPE OF DOOR SHOWN ON FLOOR PLAN |
| | DOESN'T MATCH TYPE OF DOOR SHOWN ON DOOR SCHEDULE. |
| | REVISE AS REQUIRED. |
| | |
| | G) SIZE OF WINDOW SPECIFIED ON WINDOW SCHEDULE DOESN'T |
| | MATCH SIZE OF WINDOW SHOWN ON BUILDING INFORMATION |
| | CHART. REVISE AS REQUIRED. |
| | |
| | H) NOTE INSIDE FOUNDATION PLAN CALLS FOR 48" MAX. |
| | SPACING FOR VERTICAL REINFORCEMENT BETWEEN FILLED |
| | CELLS. FOUNDATION PLAN AND FLOOR PLANS SHOW SOME AREAS |
| | WHERE THE THE MAX. VERTICAL SPACING OF FILLED CELLS |
| | EXCEED THE 48". REVISE AS REQUIRED. |
| | |
| | I) FOUNDATION NOTE #4 CALLS FOR 2,000 PSF SOIL BEARING |
| | CAPACITY, WHILE NOTE INSIDE FOUNDATION PLAN CALLS FOR |
| | 2500 SOIL BEARING CAPACITY. REVISE AS REQUIRED. |
| | |
| | J) REVISE BUILDING WIDTH AND BUILDING LENGTH DIMENSIONS |
| | SHOWN ON BUILDING INFORMATION CHART. SEE FLOOR PLANS |
| | FOR ACTUAL DIMENSIONS. |
| | |
| | K) REVISE WIDTH OF END ZONE SHOWN ON BUILDING |
| | INFORMATION CHART. SEE NOTE A ON FIGURE R301.2(8) OF |
| | 2004 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| | |
| | 12- SHEET A2: |
| | A) EXTERIOR C.M.U. WALL SECTION A/A2: |
| | * WHERE IS THE ROOF SHEATHING THICKNESS TAKEN FROM?. |
| | PROVIDE ENGINEERING CALCULATIONS SHOWING THAT SPECIFIED |
| | ROOF SHEATHING THICKNESS WILL RESIST ALL THE DESIGN |
| | LOADS OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | ** FOOTING SPECIFICATIONS DON'T MATCH FOOTING |
| | SPECIFICATION SHOWN ON FOOTING SCHEDULE ON SHEET A1. |
| | REVISE AS REQUIRED. |
| | |
| | *** SPECIFY MIN. FOOTING DEPTH AS REQUIRED BY SEC. |
| | R3403.1.4 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) REVISE OPENINGS DESIGN PRESSURES SHOWN ON THE |
| | EXTERIOR ELEVATIONS. COORDINATE WITH ITEM 11D ABOVE. |
| | |
| | C) INTERIOR WALL SECTION B/A2: THERE ARE TWO DIFFERENT |
| | WALL FINISHES SHOWN N THE SAME DETAIL. REVISE/CLARIFY |
| | AS REQUIRED. |
| | |
| | 13- SHEET A3: |
| | A) REVISE NUMBER/SIZE OF NAILS AND UPLIFT LOADS SHOWN |
| | ON TRUSS CONNECTORS SPECIFIED ON ROOF FRAMING PLAN. SEE |
| | CONNECTOR PRODUCT APPROVAL AND REVISE AS REQUIRED. |
| | |
| | B) ROOF SHEATHING: |
| | * COORDINATE TYPE AND SIZE OF NAIL SHOWN ON PLYWOOD |
| | SHEATHING FASTENER SCHEDULE AND THREE DIMENSIONAL ROOF |
| | PLAN. |
| | NOTE: MIN. NAIL TYPE TO BE USED IS 8D RING SHANK NAILS. |
| | SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | ** IDENTIFY ROOF ZONE #3 ON ROOF FRAMING PLAN AND |
| | SPECIFY MIN. NAILING TYPE AND SPACING USED AS REQUIRED |
| | BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | *** ZONE 3 IS 4'-0" MIN. SEE FIGURE 301.2(8) OF 2004 |
| | FLORIDA RESIDENTIAL CODE. REVISE GABLE NOTE AS |
| | REQUIRED. |
| | |
| | 14- PLEASE, RETURN REVIEWED SET OF DRAWINGS AFTER |
| | CORRECTIONS ARE DONE TO ORIGINAL DRAWINGS TO EXPEDITE |
| | THE REVIEW PROCESS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |