2009-01-09 16:56:30NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY TO VERIFY IF IMPACT FEES ARE DUE AND HOW MUCH
 CREDIT IS GIVEN FOR THE EXISTING HOUSE. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- NEED TO OBTAIN A SEPARATE PERMIT FOR THE DEMOLITION
 OF THE EXISTING HOUSE.
  
 4- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW. VALUATION WAS UPDATED AS REQUIRED BY SEC.
 108.3 OF CITY AMENDMENTS TO FBC 2004 TO $128,668.
 THEREFORE, OWES $2161.79 FOR UPDATED VALUATION AND
 RADON FEES.
  
 5- PLANS TO SPECIFY ALL LIVE AND DEAD LOADS AS REQUIRED
 BY SEC. R301.1 AND TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE. NOTE: ATTIC LIVE LOADS NEED TO BE
 INCLUDED ALSO.
  
 6- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) PRECAST LINTELS AS SHOWN ON PLANS.
  
 B) ENTRY DOOR AND KITCHEN AND BEDROOM EXTERIOR DOORS.
 CLEARLY IDENTIFY WHICH PRODUCT APPROVAL IS FOR THE
 ENTRY AND ALL OTHER OPENINGS.
 ***NOTE: NOA 02-1211.10 SUBMITTED EXPIRED ON JULY 17,
 2008. NEED TO PROVIDE CURRENT PRODUCT APPROVAL.
  
 C) HURRICANE SHUTTERS: PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. COMPLETE ALL THE
 INFORMATION AND CLEARLY MARK ON SHUTTERS DRAWINGS
 SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNTED, BUILD
 OUT, ETC) AND SPECIFIC ANCHOR TYPE AND SPACING TO BE
 USED.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- ENERGY CALCULATIONS: OWNER/AGENT TO SIGN AND DATE
 BOTTOM OF FORM.
  
 9- SINCE THE ENERGY CALCULATIONS ARE TAKEN THE CEILING
 FAN CREDIT, THEN THE ELECTRICAL PLAN NEEDS TO SHOW SIZE
 OF CEILING FANS AS REQUIRED BY TABLE 13-607.1.A.1 OF
 FBC 2004. AND, THEY NEED TO BE INSTALLED FOR
 INSPECTION.
  
 10- PROVIDE DRAINAGE PLAN TO SHOW COMPLIANCE WITH SEC.
 R401.3 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 11- SHEET A1:
 A) BEDROOM EGRESS WINDOWS SH-24 DON'T COMPLY WITH MIN.
 OPENING HEIGHT OF SEC. R310.1.2 OF 2004 FLORIDA
 RESIDENTIAL CODE. REVISE WINDOW SIZE AND WINDOW OPENING
 DIMENSIONS SHOWN ON WINDOW SCHEDULE.
  
 B) SPECIFY ATTIC SIZE TO SHOW COMPLIANCE WITH SEC. R807
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) WINDOW BY TUB AREA ON BOTH BATHROOMS TO HAVE SAFETY
 GLASS AS REQUIRED BY SEC. R308.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 D) DESIGN PRESSURES SPECIFIED FOR DOOR AND WINDOWS
 DON'T CORRESPOND TO EXPOSURE "C" AS SHOWN ON BUILDING
 INFORMATION CHART. REVISE AS REQUIRED.
 ALSO, DESIGN PRESSURES SHOWN ON WINDOW/ DOOR SCHEDULES
 AND EXTERIOR ELEVATIONS ON SHEETS A2 AND A3 DON'T MATCH
 DESIGN PRESSURES SHOWN ON BUILDING INFORMATION CHART.
 REVISE AS REQUIRED.
  
 E) CLARIFY DOOR HEIGHT OF DOORS SHOWN ON THE DOOR
 SCHEDULE. ENTRY DOOR TO BE MIN. 3'-0" WIDE BY 6'-8"
 HEIGHT AS REQUIRED BY SEC. R311.4.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 F) MASTER BATHROOM TYPE OF DOOR SHOWN ON FLOOR PLAN
 DOESN'T MATCH TYPE OF DOOR SHOWN ON DOOR SCHEDULE.
 REVISE AS REQUIRED.
  
 G) SIZE OF WINDOW SPECIFIED ON WINDOW SCHEDULE DOESN'T
 MATCH SIZE OF WINDOW SHOWN ON BUILDING INFORMATION
 CHART. REVISE AS REQUIRED.
  
 H) NOTE INSIDE FOUNDATION PLAN CALLS FOR 48" MAX.
 SPACING FOR VERTICAL REINFORCEMENT BETWEEN FILLED
 CELLS. FOUNDATION PLAN AND FLOOR PLANS SHOW SOME AREAS
 WHERE THE THE MAX. VERTICAL SPACING OF FILLED CELLS
 EXCEED THE 48". REVISE AS REQUIRED.
  
 I) FOUNDATION NOTE #4 CALLS FOR 2,000 PSF SOIL BEARING
 CAPACITY, WHILE NOTE INSIDE FOUNDATION PLAN CALLS FOR
 2500 SOIL BEARING CAPACITY. REVISE AS REQUIRED.
  
 J) REVISE BUILDING WIDTH AND BUILDING LENGTH DIMENSIONS
 SHOWN ON BUILDING INFORMATION CHART. SEE FLOOR PLANS
 FOR ACTUAL DIMENSIONS.
  
 K) REVISE WIDTH OF END ZONE SHOWN ON BUILDING
 INFORMATION CHART. SEE NOTE A ON FIGURE R301.2(8) OF
 2004 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 12- SHEET A2:
 A) EXTERIOR C.M.U. WALL SECTION A/A2:
 * WHERE IS THE ROOF SHEATHING THICKNESS TAKEN FROM?.
 PROVIDE ENGINEERING CALCULATIONS SHOWING THAT SPECIFIED
 ROOF SHEATHING THICKNESS WILL RESIST ALL THE DESIGN
 LOADS OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 ** FOOTING SPECIFICATIONS DON'T MATCH FOOTING
 SPECIFICATION SHOWN ON FOOTING SCHEDULE ON SHEET A1.
 REVISE AS REQUIRED.
  
 *** SPECIFY MIN. FOOTING DEPTH AS REQUIRED BY SEC.
 R3403.1.4 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) REVISE OPENINGS DESIGN PRESSURES SHOWN ON THE
 EXTERIOR ELEVATIONS. COORDINATE WITH ITEM 11D ABOVE.
  
 C) INTERIOR WALL SECTION B/A2: THERE ARE TWO DIFFERENT
 WALL FINISHES SHOWN N THE SAME DETAIL. REVISE/CLARIFY
 AS REQUIRED.
  
 13- SHEET A3:
 A) REVISE NUMBER/SIZE OF NAILS AND UPLIFT LOADS SHOWN
 ON TRUSS CONNECTORS SPECIFIED ON ROOF FRAMING PLAN. SEE
 CONNECTOR PRODUCT APPROVAL AND REVISE AS REQUIRED.
  
 B) ROOF SHEATHING:
 * COORDINATE TYPE AND SIZE OF NAIL SHOWN ON PLYWOOD
 SHEATHING FASTENER SCHEDULE AND THREE DIMENSIONAL ROOF
 PLAN.
 NOTE: MIN. NAIL TYPE TO BE USED IS 8D RING SHANK NAILS.
 SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 ** IDENTIFY ROOF ZONE #3 ON ROOF FRAMING PLAN AND
 SPECIFY MIN. NAILING TYPE AND SPACING USED AS REQUIRED
 BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 *** ZONE 3 IS 4'-0" MIN. SEE FIGURE 301.2(8) OF 2004
 FLORIDA RESIDENTIAL CODE. REVISE GABLE NOTE AS
 REQUIRED.
  
 14- PLEASE, RETURN REVIEWED SET OF DRAWINGS AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DRAWINGS TO EXPEDITE
 THE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712