Plan Review Notes
Plan Review Notes For Permit 08120283
Permit Number 08120283
Review Stop E
Sequence Number 2
Notes
Date Text
2009-02-02 12:09:15** DENIED **
  
 ** PLEASE SEE SOME ITEMS FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING. A CALL WAS PLACED TO THE
 ENGINEER OF RECORD TO GO OVER SOME OF THESE ITEMS. THE
 ENGINEER WILL LOOK INTO THE PLANS.
  
  
 1) NOTE: PLEASE SEE 13-415.2, 13-415.2.B.2,
 13-415.2.ABC.1.1, .1.2 FOR REQUIRED LIGHTING
 PERFORMANCE CALCULATIONS.
 THE FOLLOWING ARE SOME ITEMS WHICH IS NOT CONSISTENT
 WITH NOTES ON PLANS AND WHAT NEEDS TO BE SHOWN. THIS
 ALSO AFFECT THE LIGHTING CONTROLS WHICH WILL BE NOTED
 BELOW IN NOTE #2.
  
 FOR EXAMPLE: THE TOTAL DESIGN WATTAGE LISTED IN NOTE #1
 IS 15,016. THIS MUST BE A MISPRINT. THE TOTAL LISTED
 ABOVE IS 1545.
  
 FOR EXAMPLE: THE NOTES MENTIONS THE ACCENT AND DISPLAY
 LIGHTING IS NOT INCLUDED PER 13-415.B.2(1). THIS IS NOT
 A SECTION IN THE FBC. IF THIS NOTE IS MEANT TO
 REFERENCE 13-415.2.ABC.1 FOR DISPLAY AND ACCENT
 LIGHTING WHICH IS NOTED AS EXEMPT IN THE ENERGY CODE.
 PLEASE SEE THE LAST SENTENCE IN THE FIRST LINE IS THIS
 EXEMPTION IS ONLY FOR GALLERIES, MUSEUMS AND MONUMENTS.
 AS THIS OCCUPANCY IS NOT EITHER OF THESE THIS EXEMPTION
 MAY NOT BE USED. PLEASE RE-CONFIGURE AND SHOW WITH
 LIGHTING FIGURED INTO THE OVER ALL BASED ON SQ FT OF
 THOSE SPACES. SEE 13-415.2.B.2 FOR THE ADDITIONAL
 ALLOWANCE
  
 FOR EXAMPLE: PLEASE SEE THE TABLE OF CALCULATIONS WHICH
 LIST A SPACE AS RETAIL. BASED ON CHAPTER 3 OF THE FBC
 THIS IS A BUSINESS OCCUPANCY WHICH WILL ALLOW 1.1 AND
 NOT 1.7. PLEASE RE-CONFIGURE.
  
 FOR EXAMPLE: THE PLANS SHOW TRACK LIGHTING AND FIXTURES
 HOWEVER THEY ARE NOT IDENTIFIED OR SPECIFIED. UPON
 CONVERSATION WITH ENGINEER IT WAS BROUGHT UP THAT A
 FIXTURE WAS NOT KNOWN AT THIS TIME. PLEASE COME UP WITH
 SOME SORT OF FIXTURE TO SHOW MINIMUM COMPLIANCE AT THIS
 TIME. THE FIXTURE TYPE MAY ALWAYS BE REVISED AT A LATER
 DATE. THIS WILL ALLOW PERMIT ISSUANCE AND THE PROJECT
 TO MOVE FORWARD.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.3 FOR THE REQUIRED
 CONTROLS WHEN USING DISPLAY OR ACCENT LIGHTING OR TASK
 LIGHTING. MOST OF THE TASK FIXTURES DO HAVE THE
 SEPARATE REQUIRED CONTROLS ALREADY SHOWN ON THE PLANS.
 ( THIS IS NOTED AS OCCUPANCY IN SOME AREAS IS STATE AS
 RETAIL.
  
 3) NOTE: A COMMENT NOT MADE ON PREVIOUS REVIEW. PLEASE
 BE SURE THE PLANS STATE THE MINIMUM CODE PER 2005
 NFPA-70 (NEC). NO EDITION OF THE NEC IS NOTED.
 THE PLANS ALSO STATE PALM BEACH COUNTY FOR AMENDED
 CODES.
  
 4) NOTE: A COMMENT NOT MADE ON THE PREVIOUS REVIEW.
 PLEASE BE SURE TO LIST THE HORN, STROBE LEVELS FOR ADA
 COMPLIANCE. 11-4.28.1, .2, .3(4).
 THIS IS BUILDING CODE REQUIREMENT WHICH DOES AFFECT THE
 ELECTRICAL PLANS. PLEASE ADJUST EVEN IF COMMENT IS NOT
 MADE OTHER TRADES.
  
 5) NOTE: THE LOAD CALCULATIONS HAVE BEEN REVISED. IT IS
 NOT CLEAR WHAT CONTINUOUS LOADS ARE BEING FIGURED.
 PLEASE INDICATE. LIGHTING AND STORAGE TYPE WATER HEATER
 IS CONSIDERED CONTINUOUS LOADS.
 215.3,230.42,220,422.13
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  