| 2009-02-02 12:09:15 | ** DENIED ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM THE PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. A CALL WAS PLACED TO THE |
| | ENGINEER OF RECORD TO GO OVER SOME OF THESE ITEMS. THE |
| | ENGINEER WILL LOOK INTO THE PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE 13-415.2, 13-415.2.B.2, |
| | 13-415.2.ABC.1.1, .1.2 FOR REQUIRED LIGHTING |
| | PERFORMANCE CALCULATIONS. |
| | THE FOLLOWING ARE SOME ITEMS WHICH IS NOT CONSISTENT |
| | WITH NOTES ON PLANS AND WHAT NEEDS TO BE SHOWN. THIS |
| | ALSO AFFECT THE LIGHTING CONTROLS WHICH WILL BE NOTED |
| | BELOW IN NOTE #2. |
| | |
| | FOR EXAMPLE: THE TOTAL DESIGN WATTAGE LISTED IN NOTE #1 |
| | IS 15,016. THIS MUST BE A MISPRINT. THE TOTAL LISTED |
| | ABOVE IS 1545. |
| | |
| | FOR EXAMPLE: THE NOTES MENTIONS THE ACCENT AND DISPLAY |
| | LIGHTING IS NOT INCLUDED PER 13-415.B.2(1). THIS IS NOT |
| | A SECTION IN THE FBC. IF THIS NOTE IS MEANT TO |
| | REFERENCE 13-415.2.ABC.1 FOR DISPLAY AND ACCENT |
| | LIGHTING WHICH IS NOTED AS EXEMPT IN THE ENERGY CODE. |
| | PLEASE SEE THE LAST SENTENCE IN THE FIRST LINE IS THIS |
| | EXEMPTION IS ONLY FOR GALLERIES, MUSEUMS AND MONUMENTS. |
| | AS THIS OCCUPANCY IS NOT EITHER OF THESE THIS EXEMPTION |
| | MAY NOT BE USED. PLEASE RE-CONFIGURE AND SHOW WITH |
| | LIGHTING FIGURED INTO THE OVER ALL BASED ON SQ FT OF |
| | THOSE SPACES. SEE 13-415.2.B.2 FOR THE ADDITIONAL |
| | ALLOWANCE |
| | |
| | FOR EXAMPLE: PLEASE SEE THE TABLE OF CALCULATIONS WHICH |
| | LIST A SPACE AS RETAIL. BASED ON CHAPTER 3 OF THE FBC |
| | THIS IS A BUSINESS OCCUPANCY WHICH WILL ALLOW 1.1 AND |
| | NOT 1.7. PLEASE RE-CONFIGURE. |
| | |
| | FOR EXAMPLE: THE PLANS SHOW TRACK LIGHTING AND FIXTURES |
| | HOWEVER THEY ARE NOT IDENTIFIED OR SPECIFIED. UPON |
| | CONVERSATION WITH ENGINEER IT WAS BROUGHT UP THAT A |
| | FIXTURE WAS NOT KNOWN AT THIS TIME. PLEASE COME UP WITH |
| | SOME SORT OF FIXTURE TO SHOW MINIMUM COMPLIANCE AT THIS |
| | TIME. THE FIXTURE TYPE MAY ALWAYS BE REVISED AT A LATER |
| | DATE. THIS WILL ALLOW PERMIT ISSUANCE AND THE PROJECT |
| | TO MOVE FORWARD. |
| | |
| | 2) NOTE: PLEASE SEE 13-415.1.ABC.1.3 FOR THE REQUIRED |
| | CONTROLS WHEN USING DISPLAY OR ACCENT LIGHTING OR TASK |
| | LIGHTING. MOST OF THE TASK FIXTURES DO HAVE THE |
| | SEPARATE REQUIRED CONTROLS ALREADY SHOWN ON THE PLANS. |
| | ( THIS IS NOTED AS OCCUPANCY IN SOME AREAS IS STATE AS |
| | RETAIL. |
| | |
| | 3) NOTE: A COMMENT NOT MADE ON PREVIOUS REVIEW. PLEASE |
| | BE SURE THE PLANS STATE THE MINIMUM CODE PER 2005 |
| | NFPA-70 (NEC). NO EDITION OF THE NEC IS NOTED. |
| | THE PLANS ALSO STATE PALM BEACH COUNTY FOR AMENDED |
| | CODES. |
| | |
| | 4) NOTE: A COMMENT NOT MADE ON THE PREVIOUS REVIEW. |
| | PLEASE BE SURE TO LIST THE HORN, STROBE LEVELS FOR ADA |
| | COMPLIANCE. 11-4.28.1, .2, .3(4). |
| | THIS IS BUILDING CODE REQUIREMENT WHICH DOES AFFECT THE |
| | ELECTRICAL PLANS. PLEASE ADJUST EVEN IF COMMENT IS NOT |
| | MADE OTHER TRADES. |
| | |
| | 5) NOTE: THE LOAD CALCULATIONS HAVE BEEN REVISED. IT IS |
| | NOT CLEAR WHAT CONTINUOUS LOADS ARE BEING FIGURED. |
| | PLEASE INDICATE. LIGHTING AND STORAGE TYPE WATER HEATER |
| | IS CONSIDERED CONTINUOUS LOADS. |
| | 215.3,230.42,220,422.13 |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |