Plan Review Notes
Plan Review Notes For Permit 08120283
Permit Number 08120283
Review Stop M
Sequence Number 1
Notes
Date Text
2009-01-10 15:18:11REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. FLEX HANGER DETAIL INDICATES 1" HANGER STRAP USED
 FOR SUPPORT OF FLEX DUCT. IN NO CASE SHALL THE MATERIAL
 SUPPORTING FLEXIBLE DUCT THAT IS IN DIRECT CONTACT WITH
 IT BE LESS THAN 1 1/2 INCHES WIDE IN ACCORDANCE WITH
 FBCM 603.5.6.6(6).
  
 2. PLEASE PROVIDE DETAILED OUTSIDE AIR CALCULATIONS
 WITH OCCUPANCY CLASSIFICATIONS INDICATED AND BROKEN
 DOWN BY SPACES SERVED. ALSO, PLEASE INDICATE THE
 VENTILATION BASIS FOR DESIGN. INDICATE IETHER FBCM
 403.3 OR AHSRAE 62.1-2004.
  
 3. NOTE ON PAGE A2 REFLECTIVE CEILING PLAN INDICATES
 EXPOSED CEILING AREAS RE TO BE PAINTED. ANY DUCT
 INSULATION IN THIS AREA, EITHER RIGID OR FLEX, SHALL
 NOT BE PAINTED AS THIS WILL NEGATE THE REQUIRED UL 181
 LISTING OF THESE PRODUCTS RELATED TO FLAME SPREAD AND
 SMOKE DEVELOPMENT RATING. THIS APPLIES TO NEW AND
 EXISTING DUCTS. FBCM 603.4.
 NOTE: ANY EXPOSED METALLIC DUCTS IN THIS AREA IS NOT
 REQUIRED TO BE INSULATED AND MAY BE PAINTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: