| Plan Review Notes For Permit 08120283 |
| Permit Number |
08120283 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-10 15:18:11 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. FLEX HANGER DETAIL INDICATES 1" HANGER STRAP USED | | | FOR SUPPORT OF FLEX DUCT. IN NO CASE SHALL THE MATERIAL | | | SUPPORTING FLEXIBLE DUCT THAT IS IN DIRECT CONTACT WITH | | | IT BE LESS THAN 1 1/2 INCHES WIDE IN ACCORDANCE WITH | | | FBCM 603.5.6.6(6). | | | | | | 2. PLEASE PROVIDE DETAILED OUTSIDE AIR CALCULATIONS | | | WITH OCCUPANCY CLASSIFICATIONS INDICATED AND BROKEN | | | DOWN BY SPACES SERVED. ALSO, PLEASE INDICATE THE | | | VENTILATION BASIS FOR DESIGN. INDICATE IETHER FBCM | | | 403.3 OR AHSRAE 62.1-2004. | | | | | | 3. NOTE ON PAGE A2 REFLECTIVE CEILING PLAN INDICATES | | | EXPOSED CEILING AREAS RE TO BE PAINTED. ANY DUCT | | | INSULATION IN THIS AREA, EITHER RIGID OR FLEX, SHALL | | | NOT BE PAINTED AS THIS WILL NEGATE THE REQUIRED UL 181 | | | LISTING OF THESE PRODUCTS RELATED TO FLAME SPREAD AND | | | SMOKE DEVELOPMENT RATING. THIS APPLIES TO NEW AND | | | EXISTING DUCTS. FBCM 603.4. | | | NOTE: ANY EXPOSED METALLIC DUCTS IN THIS AREA IS NOT | | | REQUIRED TO BE INSULATED AND MAY BE PAINTED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|