| Plan Review Notes For Permit 08120283 |
| Permit Number |
08120283 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-12-26 10:54:54 | ***PROVISO*** | | | | | | PLANS WILL BE STAMPED WHEN RETURNED WITH | | | CORRECTIONS/CLARRIFICATION FOR THESE AND OTHER REVIEW | | | COMMENTS. | | | | | | 1) PLEASE INDICATE THE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING THAT IS SPECIFIC | | | TO THIS PROJECT. SHEET A3 | | | | | | 2) PROVIDE FIRE SPRINKLER HEAD LAYOUT THAT MAY BE SHOWN | | | ON THE REFLECTED CEILING PLAN. IN ADDITION, SEPARATE | | | SHOP DRAWINGS AND PERMIT ALONG WITH MANUFACTURER | | | SPECIFICATIONS ARE REQUIRED PRIOR TO EQUIPMENT | | | INSTALLATION. | | | | | | 3) SHEET E1 INDICATES (1) NEW HORN STROBE INSIDE | | | PATIENT BATHROOM 115 AND EXISTING EQUIPMENT NEXT TO THE | | | RECEPTION EXIT DOOR. ARE THERE ANY OTHER DEVICES | | | PROPOSED FOR COMMON AREAS OR HALLWAYS? | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|