| 2008-12-24 13:30:17 | ** DENIED REVIEW** |
| | |
| | |
| | 1) NOTE: LIGHTING CONTROLS FOR NEW INSTALLED SHALL |
| | COMPLY WITH FBC 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | SOME SHOWN IS OK FOR COMPLIANCE HOWEVER SOME OTHER NEW |
| | DEVICES SHOWN ARE NOT. |
| | PLEASE |
| | |
| | 2) NOTE: THE LIGHTING PERFORMANCE CALCULATIONS AS |
| | SUBMITTED ARE NOT CODE COMPLIANT AND/OR CAN NOT BE |
| | DETERMINED AS COMPLAINT UNTIL MORE INFORMATION IS |
| | PROVIDED. THE PROPOSED NEW ADDITIONAL LIGHTING AS |
| | PROPOSED IS NOT PERMITTED AT THIS TIME. INFORMATION IS |
| | NEEDED ON ALL EXISTING LIGHTING BEFORE AN ALLOWANCE OF |
| | PROPOSED NEW LIGHTING MAY BE INSTALLED |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2. |
| | PLANS AS SUBMITTED INDICATE A BUILDING AREA METHOD FOR |
| | ALLOWANCE AND DESIGN. YOU MUST SHOW ALL EXISTING |
| | LIGHTING INFORMATION TO DETERMINE IF THE ADDITION OF |
| | NEW LIGHTING IS PERMITTED. |
| | ** PLEASE CALL TO GO OVER IF THERE ARE ANY QUESTIONS. |
| | |
| | 3) NOTE: PLEASE COMPLETE PANELS/CIRCUITS ETC ON PLANS |
| | AND COORDINATE. AN EXAMPLE OF THIS IS THE SIGN CIRCUIT |
| | WHICH IS NOTED ON THE LIGHTING PLANS AS EXISTING |
| | CIRCUIT L-36 HOWEVER CIRCUIT 36 ON THE L PANEL IS |
| | BLANK. NO CIRCUIT, NO LOAD, NO OVER CURRENT PROTECTION |
| | ETC. |
| | PLEASE SEE 600.5 FOR MINIMUM LOADS AND CIRCUIT SIZE FOR |
| | SIGNS. |
| | PLEASE SEE 408.4 FOR PANEL SCHEDULE REQUIRED TO BE |
| | ACCURATE. |
| | PLEASE SEE FBC 106.1.1 FOR CLARITY OF PLANS AND |
| | COORDINATION. |
| | ** THIS IS ONE EXAMPLE GIVEN ONLY. |
| | |
| | |
| | 4) NOTE: PLEASE SEE NEC 517 FOR REQUIREMENTS OF WIRING |
| | OF RECEPTACLE CIRCUITS FOR REDUNDANT GROUNDING. PLEASE |
| | SEE 517.10 (PART II). |
| | PLEASE ALSO SEE THE OCCUPANCY SHALL COMPLY WITH ALL OF |
| | NEC 517 AS THE LOCATION ON TITLE BLOCKS CLEARLY STATE |
| | ** PLASTIC SURGERY**. |
| | |
| | |
| | |
| | ** AS THERE IS SOME INFORMATION NOT YET SUBMITTED OR |
| | SHOWN, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NTO BE MADE AT THIS TIME. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |