Plan Review Notes
Plan Review Notes For Permit 08120283
Permit Number 08120283
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-24 13:30:17** DENIED REVIEW**
  
  
 1) NOTE: LIGHTING CONTROLS FOR NEW INSTALLED SHALL
 COMPLY WITH FBC 13-415.1.ABC.1.1, .1.2 AND .1.3.
 SOME SHOWN IS OK FOR COMPLIANCE HOWEVER SOME OTHER NEW
 DEVICES SHOWN ARE NOT.
 PLEASE
  
 2) NOTE: THE LIGHTING PERFORMANCE CALCULATIONS AS
 SUBMITTED ARE NOT CODE COMPLIANT AND/OR CAN NOT BE
 DETERMINED AS COMPLAINT UNTIL MORE INFORMATION IS
 PROVIDED. THE PROPOSED NEW ADDITIONAL LIGHTING AS
 PROPOSED IS NOT PERMITTED AT THIS TIME. INFORMATION IS
 NEEDED ON ALL EXISTING LIGHTING BEFORE AN ALLOWANCE OF
 PROPOSED NEW LIGHTING MAY BE INSTALLED
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2.
 PLANS AS SUBMITTED INDICATE A BUILDING AREA METHOD FOR
 ALLOWANCE AND DESIGN. YOU MUST SHOW ALL EXISTING
 LIGHTING INFORMATION TO DETERMINE IF THE ADDITION OF
 NEW LIGHTING IS PERMITTED.
 ** PLEASE CALL TO GO OVER IF THERE ARE ANY QUESTIONS.
  
 3) NOTE: PLEASE COMPLETE PANELS/CIRCUITS ETC ON PLANS
 AND COORDINATE. AN EXAMPLE OF THIS IS THE SIGN CIRCUIT
 WHICH IS NOTED ON THE LIGHTING PLANS AS EXISTING
 CIRCUIT L-36 HOWEVER CIRCUIT 36 ON THE L PANEL IS
 BLANK. NO CIRCUIT, NO LOAD, NO OVER CURRENT PROTECTION
 ETC.
 PLEASE SEE 600.5 FOR MINIMUM LOADS AND CIRCUIT SIZE FOR
 SIGNS.
 PLEASE SEE 408.4 FOR PANEL SCHEDULE REQUIRED TO BE
 ACCURATE.
 PLEASE SEE FBC 106.1.1 FOR CLARITY OF PLANS AND
 COORDINATION.
 ** THIS IS ONE EXAMPLE GIVEN ONLY.
  
  
 4) NOTE: PLEASE SEE NEC 517 FOR REQUIREMENTS OF WIRING
 OF RECEPTACLE CIRCUITS FOR REDUNDANT GROUNDING. PLEASE
 SEE 517.10 (PART II).
 PLEASE ALSO SEE THE OCCUPANCY SHALL COMPLY WITH ALL OF
 NEC 517 AS THE LOCATION ON TITLE BLOCKS CLEARLY STATE
 ** PLASTIC SURGERY**.
  
  
  
 ** AS THERE IS SOME INFORMATION NOT YET SUBMITTED OR
 SHOWN, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NTO BE MADE AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  