Plan Review Notes
Plan Review Notes For Permit 08120274
Permit Number 08120274
Review Stop E
Sequence Number 8
Notes
Date Text
2009-07-24 20:12:21 
 ** DENIED REVISIONS **
  
 1) NOTE: PLEASE SEE THE SUBMITTED SKE ELECTRICAL DETAIL
 SHEETS DO NOT CONTAIN THE RAISED SEAL AS REQUIRED PER
 FAC 61G15-23.002, FS 471.025. IN FACT ONE OF THE THREE
 SUBMITTED IS A PHOTO-COPY.
 PLEASE SUBMIT A MINIMUM OF TWO ORIGINAL SIGNED, DATED
 AND SEALED SHEETS.
  
 2) NOTE: IT WAS NOTED ON PREVIOUS REVIEWS AS A
 *HEADS-UP* ON INFORMATION TO SEE THE NEW FLORIDA
 ASME-17 FOR MINIMUM ELEVATOR CODE REQUIREMENTS.
 THIS OFFICE DOES NOT REVIEW FOR THESE ITEMS FOR MINIMUM
 CODE COMPLIANCE HOWEVER BASED ON THE CODE REQUIREMENTS
 KNOWN TO THIS REVIEWER LIGHTING IN AREAS OF THE
 ELEVATOR LOBBY AS SHOWN WOULD NOT MEET MINIMUM. AN
 INSPECTION BY THE STATE ELEVATOR INSPECTOR WOULD NOT BE
 THE TIME TO FIND OUT ITEMS WHICH WOULD THEN NEED TO BE
 ADDED WHICH WOULD DELAY A TCO OR CO.
 ** SEE LIGHTING LEVELS FOR SILLS AND AT LANDINGS.
  
 ** THIS WILL AFFECT LPC. 13-415.2.ABC.1.1,.1.2,
 13-415.2.
  
 ** THE LIGHTING SHOWN ON THE REFLECTED CEILING PLAN OF
 THE ARCHITECTURAL PLANS DOES NOT COORDINATE WITH THE
 ELECTRICAL PLANS FOR THE ELEVATOR LOBBY.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  