Plan Review Notes
Plan Review Notes For Permit 08120274
Permit Number 08120274
Review Stop P
Sequence Number 2
Notes
Date Text
2009-04-03 17:32:51DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A1.1 SHOW ACCESSIBILITY COMPLIANCE WITH THE
 FOLLOWING:
  
 ___W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ___URINAL:
 A. 11-4.18.2 HEIGHT
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 B. 11-4.18.3 CLEAR FLOOR SPACE
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 C. 11-4.18.4 FLUSH CONTROLS
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ___TOILET ROOMS:
 A. 11-4.22.3 THE UNOBSTRUCTED TURNING AREAS ARE NOT
 SHOWN IN THE TOILET ROOMS OF TOILET ROOMS 115 & 116.
 THE TURNING AREA SHALL BE SHOWN IN THE TOILET ROOM, NOT
 THE ACCESSIBLE STALL.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ___SINK:
 A. 11-4.24.2 HEIGHT
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 B. 11-4.24.3 KNEE CLEARANCE
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 C. 11-4.24.5 CLEAR FLOOR SPACE - PARALLEL APPROACH
 SHOWN BUT FORWARD APPROACH REQUIRED. SUBMIT AN
 ELEVATION SHOWING THE REQUIRED OPENING. CABINET DOORS
 ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2. SHT M1.2 PER TABLE 403.1 TWO DRINKING FOUNTAINS ARE
 REQUIRED. THE MODEL INDICATED SHOWS ONE TRAP AND ONE
 SUPPLY TO THE HI/LOW DRINKING FOUNTAIN. EACH FIXTURE
 SHALL HAVE ITS OWN TRAP AND WATER SUPPLY SO THE
 HIGH/LOW INDICATED IS CONSIDERED ONE FIXTURE. PLEASE
 INDICATE THE LOCATION OF THE SECOND DRINKING FOUNTAIN.
 SECTIONS 410.1 & 1002.1. (WATER ISOMETRIC ONLY SHOWS
 ONE SUPPLY ALSO).
 ****NO WRITTEN RESPONSE, BUT THE SANITARY RISER SHOWS 2
 TRAPS, BUT THIS DOES NOT REFLECT THE FLOOR PLAN WHICH
 SHOWS 1 TRAP. THE WATER SUPPLY RISER DIAGRAM ONLY SHOWS
 ONE WATER SUPPLY. TWO DRINKING FOUNTAINS ARE REQUIRED.
  
 3. SHT M1.2 WATER HEATER DETAIL. PLEASE SUBMIT THE
 MANUFACTURE SPECIFICATION AND MODEL FOR THE THERMAL
 EXPANSION TANK. SUBMIT MANUFACTURE CALCULATIONS OR
 SIZING CHART FOR THE SIZING OF THE EXPANSION TANK.
 SECTION 617.3.2.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ****NO RESPONSE, COMMENT NOT ADDRESSED. NO TRANSMITTAL
 LETTER SUBMITTED, NOR WAS ONE SET OF VOIDED SHEETS
 SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved