| Date |
Text |
| 2009-04-03 17:32:51 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SHT A1.1 SHOW ACCESSIBILITY COMPLIANCE WITH THE |
| | FOLLOWING: |
| | |
| | ___W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | ___URINAL: |
| | A. 11-4.18.2 HEIGHT |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | ___TOILET ROOMS: |
| | A. 11-4.22.3 THE UNOBSTRUCTED TURNING AREAS ARE NOT |
| | SHOWN IN THE TOILET ROOMS OF TOILET ROOMS 115 & 116. |
| | THE TURNING AREA SHALL BE SHOWN IN THE TOILET ROOM, NOT |
| | THE ACCESSIBLE STALL. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | ___SINK: |
| | A. 11-4.24.2 HEIGHT |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | B. 11-4.24.3 KNEE CLEARANCE |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | C. 11-4.24.5 CLEAR FLOOR SPACE - PARALLEL APPROACH |
| | SHOWN BUT FORWARD APPROACH REQUIRED. SUBMIT AN |
| | ELEVATION SHOWING THE REQUIRED OPENING. CABINET DOORS |
| | ARE NOT APPROVED IN THE CLEAR FLOOR SPACE. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 2. SHT M1.2 PER TABLE 403.1 TWO DRINKING FOUNTAINS ARE |
| | REQUIRED. THE MODEL INDICATED SHOWS ONE TRAP AND ONE |
| | SUPPLY TO THE HI/LOW DRINKING FOUNTAIN. EACH FIXTURE |
| | SHALL HAVE ITS OWN TRAP AND WATER SUPPLY SO THE |
| | HIGH/LOW INDICATED IS CONSIDERED ONE FIXTURE. PLEASE |
| | INDICATE THE LOCATION OF THE SECOND DRINKING FOUNTAIN. |
| | SECTIONS 410.1 & 1002.1. (WATER ISOMETRIC ONLY SHOWS |
| | ONE SUPPLY ALSO). |
| | ****NO WRITTEN RESPONSE, BUT THE SANITARY RISER SHOWS 2 |
| | TRAPS, BUT THIS DOES NOT REFLECT THE FLOOR PLAN WHICH |
| | SHOWS 1 TRAP. THE WATER SUPPLY RISER DIAGRAM ONLY SHOWS |
| | ONE WATER SUPPLY. TWO DRINKING FOUNTAINS ARE REQUIRED. |
| | |
| | 3. SHT M1.2 WATER HEATER DETAIL. PLEASE SUBMIT THE |
| | MANUFACTURE SPECIFICATION AND MODEL FOR THE THERMAL |
| | EXPANSION TANK. SUBMIT MANUFACTURE CALCULATIONS OR |
| | SIZING CHART FOR THE SIZING OF THE EXPANSION TANK. |
| | SECTION 617.3.2. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. NO TRANSMITTAL |
| | LETTER SUBMITTED, NOR WAS ONE SET OF VOIDED SHEETS |
| | SUBMITTED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |