Plan Review Notes
Plan Review Notes For Permit 08120274
Permit Number 08120274
Review Stop E
Sequence Number 2
Notes
Date Text
2009-04-02 19:09:021) NOTE: NO MINIMUM CODES STATED ON ELECTRICAL PLANS
 FOR WHICH PROJECT IS UNDER. THE A SHEETS DO NOT CONTAIN
 THE CURRENT MINIMUM REQUIRED CODES AS NEEDED BELOW.
 PLEASE SEE THAT THE FOLLOWING ARE ON PLANS.
  
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE NEC 220.12,220.14, 220.42, 220.44
 ETC LOAD CALCULATIONS FOR PLANS NEED TO MEET THE NEC.
 THE LOAD CALCULATIONS STATE THE MAXIMUM WATTAGE
 ALLOWANCE FOR LIGHTING PER THE FBC. THE SIZING OF
 LIGHTING PANELS FOR FEEDERS, BRANCH CIRCUITS AND
 SERVICE LOAD CALCULATIONS ARE BASE DON THE NEC NOT THE
 FLORIDA BUILDING CODE. THE MINIMUM LIGHTING WATTS PER
 SQUARE FOOT WHEN SIZING THE ABOVE MUST BE PER NEC.
 PLEASE REVISE ALL.
 THIS MAY AFFECT THE SIZE OF THE PANEL.
  
 3) NOTE: AS REQUESTED ON THE PREVIOUS REVIEW THE
 MINIMUM LEVELS, HEIGHTS ETC FOR HORNS, HORN STROBE
 DEVICES SHALL MEET THE FBC CHAPTER 11. 11-4.28.1, .2
 AND .3.
 NO DEVICE LEVELS, HEIGHTS ETC WERE SHOWN ON ANY OF THE
 THREE SHEETS.
  
 4) NOTE: PLEASE SEE THE SUBMITTED FORM B FOR CHAPTER 13
 COMPLIANCE IS FROM THE NEW 2007 FBC. MIXING OF
 CALCULATIONS FROM DIFFERENT CODES IS NOT PERMITTED.
 PLANS SHOW COMPLIANCE WITH THE SPACE BY SPACE METHOD B.
 THIS IS ALL THAT IS NEEDED FOR THIS REVIEWER. PLEASE
 SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY BE NEEDED.
  
 5) NOTE: THE PLANS INDICATE AN IT ROOM WITH A
 DISCONNECT SWITCH FOR AHU, HOWEVER COMPLIANCE WITH NEC
 645, 6.4510 ETC IS NOT MET. THE ROOM MAY NOT BE CALLED
 AND IT ROOM UNLESS MEETING ALL OF THE REQUIREMENTS IN
 NEC 645.4. (1-5)
 WHEN MEETING ALL OF THESE ITEMS AS LISTED THEN THE LESS
 RESTRICTIVE WIRING METHODS PERMITTED IN 645 IS
 PERMITTED. WHEN NOT MEETING THE ABOVE SECTIONS ALL 1-5,
 THEN ALL WIRING METHODS SHALL BE PER CHAPTERS 1-4 OF
 THE NEC. PLEASE KEEP IN MIND THAT COMPANY IT OR LOW
 VOLTAGE PERSONNEL MAY WANT TO USE WIRING METHODS IN
 645, IF SO, THEN THE ROOM SHALL MEET ALL ITEMS IN 645.4
 1-5.
 IF THIS ROOM IS NOT AN IT ROOM, REVISE DESIGNATION AND
 PLEASE PLACE NOTE ON PLANS WHICH STATES * NO WIRING
 METHODS PER NEC 645 PERMITTED* OR WORDS TO THAT AFFECT.
 CALL FOR QUESTIONS.
  
 6) NOTE: THE LIFE SAFETY PLANS DO NOT CORRELATE WITH
 THE ELECTRICAL PLANS FOR EMERGENCY LIGHTING.
 THE LIFE SAFETY SHEETS ALSO STATE TO SEE ELECTRICAL
 PLANS FOR EMERGENCY LIGHTING ABOVE SOFFIT HOWEVER THE
 ELECTRICAL PLANS DO NOT INDICATE ANY EMERGENCY LIGHTING
 ABOVE SOFFIT.
 NFPA-101 7.8, 7.9
 FBC 1006.1.2
  
 7) NOTE: PLEASE KEEP IN MIND ALL OF THE NEW
 REQUIREMENTS OF ASME-17 FOR FLORIDA ELEVATOR CODE
 REQUIREMENTS STILL MUST BE MET. THIS IS ONLY NOTED FOR
 INFORMATIONAL PURPOSE. THIS IS NOT A REVIEW COMMENT FOR
 THIS TRADE. THERE IS ITEMS PER STATE ELEVATOR CODE
 WHICH WOULD NOT MEET CURRENT ELEVATOR CODES.
 SEE REFERENCE FROM FBC CHAPTER 30, NEC FPN TO ASME.
  
 8) NOTE: PANEL SCHEDULE FOR CIRCUITS DOES NOT MEET
 408.4. STATING RECEPTACLES WITHOUT SPECIFIC ROOM AND
 AREAS IS NOT PERMITTED. PLEASE SEE REVISED 2005 NEC AND
 COMMENTARY IN HANDBOOK.
 PLEASE REVISE.
  
 ** KEEP IN MIND FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR MINIMUM CODE COMPLIANCE.
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  