| 2009-04-02 19:09:02 | 1) NOTE: NO MINIMUM CODES STATED ON ELECTRICAL PLANS |
| | FOR WHICH PROJECT IS UNDER. THE A SHEETS DO NOT CONTAIN |
| | THE CURRENT MINIMUM REQUIRED CODES AS NEEDED BELOW. |
| | PLEASE SEE THAT THE FOLLOWING ARE ON PLANS. |
| | |
| | 2004 FBC W/2007 REVISIONS. |
| | 2003 NFPA-101 |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE NEC 220.12,220.14, 220.42, 220.44 |
| | ETC LOAD CALCULATIONS FOR PLANS NEED TO MEET THE NEC. |
| | THE LOAD CALCULATIONS STATE THE MAXIMUM WATTAGE |
| | ALLOWANCE FOR LIGHTING PER THE FBC. THE SIZING OF |
| | LIGHTING PANELS FOR FEEDERS, BRANCH CIRCUITS AND |
| | SERVICE LOAD CALCULATIONS ARE BASE DON THE NEC NOT THE |
| | FLORIDA BUILDING CODE. THE MINIMUM LIGHTING WATTS PER |
| | SQUARE FOOT WHEN SIZING THE ABOVE MUST BE PER NEC. |
| | PLEASE REVISE ALL. |
| | THIS MAY AFFECT THE SIZE OF THE PANEL. |
| | |
| | 3) NOTE: AS REQUESTED ON THE PREVIOUS REVIEW THE |
| | MINIMUM LEVELS, HEIGHTS ETC FOR HORNS, HORN STROBE |
| | DEVICES SHALL MEET THE FBC CHAPTER 11. 11-4.28.1, .2 |
| | AND .3. |
| | NO DEVICE LEVELS, HEIGHTS ETC WERE SHOWN ON ANY OF THE |
| | THREE SHEETS. |
| | |
| | 4) NOTE: PLEASE SEE THE SUBMITTED FORM B FOR CHAPTER 13 |
| | COMPLIANCE IS FROM THE NEW 2007 FBC. MIXING OF |
| | CALCULATIONS FROM DIFFERENT CODES IS NOT PERMITTED. |
| | PLANS SHOW COMPLIANCE WITH THE SPACE BY SPACE METHOD B. |
| | THIS IS ALL THAT IS NEEDED FOR THIS REVIEWER. PLEASE |
| | SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY BE NEEDED. |
| | |
| | 5) NOTE: THE PLANS INDICATE AN IT ROOM WITH A |
| | DISCONNECT SWITCH FOR AHU, HOWEVER COMPLIANCE WITH NEC |
| | 645, 6.4510 ETC IS NOT MET. THE ROOM MAY NOT BE CALLED |
| | AND IT ROOM UNLESS MEETING ALL OF THE REQUIREMENTS IN |
| | NEC 645.4. (1-5) |
| | WHEN MEETING ALL OF THESE ITEMS AS LISTED THEN THE LESS |
| | RESTRICTIVE WIRING METHODS PERMITTED IN 645 IS |
| | PERMITTED. WHEN NOT MEETING THE ABOVE SECTIONS ALL 1-5, |
| | THEN ALL WIRING METHODS SHALL BE PER CHAPTERS 1-4 OF |
| | THE NEC. PLEASE KEEP IN MIND THAT COMPANY IT OR LOW |
| | VOLTAGE PERSONNEL MAY WANT TO USE WIRING METHODS IN |
| | 645, IF SO, THEN THE ROOM SHALL MEET ALL ITEMS IN 645.4 |
| | 1-5. |
| | IF THIS ROOM IS NOT AN IT ROOM, REVISE DESIGNATION AND |
| | PLEASE PLACE NOTE ON PLANS WHICH STATES * NO WIRING |
| | METHODS PER NEC 645 PERMITTED* OR WORDS TO THAT AFFECT. |
| | CALL FOR QUESTIONS. |
| | |
| | 6) NOTE: THE LIFE SAFETY PLANS DO NOT CORRELATE WITH |
| | THE ELECTRICAL PLANS FOR EMERGENCY LIGHTING. |
| | THE LIFE SAFETY SHEETS ALSO STATE TO SEE ELECTRICAL |
| | PLANS FOR EMERGENCY LIGHTING ABOVE SOFFIT HOWEVER THE |
| | ELECTRICAL PLANS DO NOT INDICATE ANY EMERGENCY LIGHTING |
| | ABOVE SOFFIT. |
| | NFPA-101 7.8, 7.9 |
| | FBC 1006.1.2 |
| | |
| | 7) NOTE: PLEASE KEEP IN MIND ALL OF THE NEW |
| | REQUIREMENTS OF ASME-17 FOR FLORIDA ELEVATOR CODE |
| | REQUIREMENTS STILL MUST BE MET. THIS IS ONLY NOTED FOR |
| | INFORMATIONAL PURPOSE. THIS IS NOT A REVIEW COMMENT FOR |
| | THIS TRADE. THERE IS ITEMS PER STATE ELEVATOR CODE |
| | WHICH WOULD NOT MEET CURRENT ELEVATOR CODES. |
| | SEE REFERENCE FROM FBC CHAPTER 30, NEC FPN TO ASME. |
| | |
| | 8) NOTE: PANEL SCHEDULE FOR CIRCUITS DOES NOT MEET |
| | 408.4. STATING RECEPTACLES WITHOUT SPECIFIC ROOM AND |
| | AREAS IS NOT PERMITTED. PLEASE SEE REVISED 2005 NEC AND |
| | COMMENTARY IN HANDBOOK. |
| | PLEASE REVISE. |
| | |
| | ** KEEP IN MIND FS 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR MINIMUM CODE COMPLIANCE. |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |