Plan Review Notes
Plan Review Notes For Permit 08120274
Permit Number 08120274
Review Stop P
Sequence Number 1
Notes
Date Text
2009-01-29 15:15:08DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A1.1 SHOW ACCESSIBILITY COMPLIANCE WITH THE
 FOLLOWING:
  
 ___W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
  
 ___URINAL:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
  
 ___TOILET ROOMS:
 A. 11-4.22.3 THE UNOBSTRUCTED TURNING AREAS ARE NOT
 SHOWN IN THE TOILET ROOMS OF TOILET ROOMS 115 & 116.
 THE TURNING AREA SHALL BE SHOWN IN THE TOILET ROOM, NOT
 THE ACCESSIBLE STALL.
  
 ___SINK:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.5 CLEAR FLOOR SPACE - PARALLEL APPROACH
 SHOWN BUT FORWARD APPROACH REQUIRED. SUBMIT AN
 ELEVATION SHOWING THE REQUIRED OPENING. CABINET DOORS
 ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
  
 2. SHT M1.2 PER TABLE 403.1 TWO DRINKING FOUNTAINS ARE
 REQUIRED. THE MODEL INDICATED SHOWS ONE TRAP AND ONE
 SUPPLY TO THE HI/LOW DRINKING FOUNTAIN. EACH FIXTURE
 SHALL HAVE ITS OWN TRAP AND WATER SUPPLY SO THE
 HIGH/LOW INDICATED IS CONSIDERED ONE FIXTURE. PLEASE
 INDICATE THE LOCATION OF THE SECOND DRINKING FOUNTAIN.
 SECTIONS 410.1 & 1002.1. (WATER ISOMETRIC ONLY SHOWS
 ONE SUPPLY ALSO).
  
 3. SHT M1.2 WATER HEATER DETAIL. PLEASE SUBMIT THE
 MANUFACTURE SPECIFICATION AND MODEL FOR THE THERMAL
 EXPANSION TANK. SUBMIT MANUFACTURE CALCULATIONS OR
 SIZING CHART FOR THE SIZING OF THE EXPANSION TANK.
 SECTION 617.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  